ABB CDD Product Manual page 46

Concentrator data device
Table of Contents

Advertisement

Display code
Cause
LED status
Message
E018
The error is generated when a
blinking
ground leakage current is de-
green
tected in the DC section of the
Ground fault
system. This may be caused by:
a) PV module ground leakage
b) Internal inverter fault
E023
The error is generated if the DC
Blinking
component of the current sup-
green
plied to the grid exceeds the
DC Injection
threshold set by the country of
installation's applicable regula-
tion. In any case, the inverter will
automatically try to reconnect to
the grid. This may be caused by:
a) Sporadic recurrence of this
error is a sign of large grid dis-
tortions or sudden changes in
irradiance.
b) Systematic recurrence of this
error may be due to an inverter
fault.
E024
a) The alarm may occur dur-
Blinking red
ing inverter initialization and is
Internal Error
caused by the initialization of
communication between the CDD
and the MICRO inverters.
b) Systematic occurrence of this
error may be due to an inverter
fault.
Solution
See the "Verification of ground leak-
age" and "Measuring the insulation
resistance" sections for information on
how to perform checks and measure-
ments.
a) If the measured insulation resis-
tance value is less than 1KΩ, the PV
module has a ground leakage that
prevents the grid connection of the
inverter. In this case the PV module
must be replaced.
b) If the measured value exceeds
1KΩ, try connecting the MICRO invert-
er to a different PV module. If the error
persists, the alarm may be caused by
internal inverter faults. To perform this
test, the MICRO inverter Ground Fault
condition must be reset via the Web
Server.
a) Verify the grid parameters and, if
the grid voltage is strongly distorted,
please contact your grid operator to
address the problem
If the grid voltage is stable, the error
may also be due to sudden irradiance
variations. In this case, the inverter
will automatically try to reconnect to
the grid and no actions are required to
solve the problem.
b) If the grid voltage is stable, yet the
error systematically persists, the mal-
function may be caused by an internal
inverter fault
a) The alarm will automatically reset
upon connection of the inverter to the
grid, and no actions are required to
solve the problem.
b) If the error systematically persists,
the malfunction may be caused by an
internal inverter fault
- 46 -