Setting Defrosting Inhibit Period
DFTIM_OT P5
DFTIM_OTP 10
DFTIM_OT P0
– 1 0
– 5˚C
0
˚C
Notes:
(1)
The first inhibit time after operation start is set to DFTIM_FST.
(2)
From the second time onwards, the inhibit time is set according to the time required for
defrosting.
Reverse cycle operation time
[DEFCOL] : DEFTIM_COL is set.
Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor tempera-
ture is set.
Outdoor temperature