Protocol Converter G1Pr2 (Option) - Toshiba GRT100 Manual

Gr series
Hide thumbs Also See for GRT100:
Table of Contents

Advertisement

GRT100
Test
European Commission Directives

PROTOCOL CONVERTER G1PR2 (OPTION)

Ratings
Power supply:
Burden:
Communication port
RS232C interface
Connector type
Cable type
RS485 interface
Connector
Cable type
Optical interface
Operative Range:
Wavelength:
Connector type:
Fibre type:
IRIG-B
Connector
Mechanical design
Enclosure Protection
Weight
Installation
Atmospheric Environment
Temperature
Humidity
Standards
89/336/EEC
73/23/EEC
110Vdc/100Vac
220Vdc/200Vac
48Vdc
less than 20W
RS232C 9-pin D-subminiature connector female
Multi-core (straight)
Screw terminals (Phoenix Contact, FRONT type)
Twisted pair cable
less than 1.2km with 62.5/125µm GI fibre (3dB/km)
820nm
ST
62.5/125µm glass fibre
Screw terminals (Phoenix Contact, FRONT-MSTB type)
IEC60529, IP20
5 kg
Flush mounting
IEC60068-2-1/2
IEC60068-2-78
Details
Compliance with the European Commission
Electromagnetic Compatibility Directive is
demonstrated according to EN 61000-6-2 and EN
61000-6-4.
Compliance with the European Commission Low
Voltage Directive is demonstrated according to EN
50178 and EN 60255-5.
Operative range:
88 - 150Vdc of 110Vdc rated voltage
80 - 120Vac of 100Vac rated voltage
Operative range:
170 - 300Vdc of 220Vdc rated voltage
200 - 240Vac of 200Vac rated voltage
Operative range:
38.4 - 72Vdc
Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
56 days at 40°C and 93% relative humidity.