Basic error limit (operational limit at 25 °C)
Voltage in relation to output range, (+/-)
Current in relation to output range, (+/-)
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Diagnostics
Substitute values can be applied
Interrupts
Diagnostics interrupt
Diagnostics alarms
Monitoring of supply voltage
Wire break
Short-circuit
Overflow/underflow
Diagnostics indicator LED
RUN LED
ERROR LED
Monitoring of supply voltage (PWR LED)
Channel status display
For channel diagnostics
For module diagnostics
Electrical isolation
Electrical isolation of channels
Between the channels
Between the channels, in groups of
Between the channels and backplane bus
Between the channels and load voltage L+
Permitted potential difference
Between different circuits
Isolation
Isolation tested with
Distributed mode
Prioritized startup
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Analog Output Module AQ 4xU/I HF (6ES7532-5ND00-0AB0)
Manual, 03/2016, A5E36633205-AA
Technical specifications
6ES7532-5ND00-0AB0
0.06 %
0.1%
No
Yes
Yes
Yes
Yes
Yes; only for output type current
Yes; only for output type voltage
Yes
Yes; green LED
Yes; red LED
Yes; green LED
Yes; green LED
Yes; red LED
Yes; red LED
Yes
1
Yes
Yes
60 V DC / 30 V AC; Isolation measured for 120 V
AC basic isolation: Between the channels and
supply voltage L+, between the channels and the
backplane bus, between the channels
2000 V DC between the channels and the supply
voltage L+, 2000 V DC between the channels and
the backplane bus, 2000 V DC between the
channels, 707 V DC (type test) between the sup-
ply voltage L+ and the backplane bus
Yes
35 mm
147 mm
129 mm
300 g