Download Print this page

Beko BEKOMAT 13 CO Instructions For Installation And Operation Manual page 6

Advertisement

Installation • Instalación
Installation • Instalação
2
3
4
1
wrong • no correcto
incorrect • incorrecto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
6
5
6
correct • correcto
correct • correcto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1. Feed pipe and fitting at least ½"!
(internal dia > 0,51 inch)
2. No filters in feed line
3. Slope in feed line > 1%!
4. Only use ball valves!
5. Pressure: min. 12 psig or 18 psig!
(check type plate for correct pres-
sure)
6. Short pressure hose!
7. For each yard of rising slope in the
outlet line, the required minimum
pressure will increase by 1.5 psig.
8
7
The rise of the outlet line must not
exceed 17 feet!
8. Collecting line min. ¾ '' with 1% slope
9. In the case of inflow problems, install
venting line.
Note: Pressure differences!
Each condensate source must be
drained separately!
Note: Venting!
If the feed line cannot be laid with
sufficient slope, it will be necessary to
install a venting line!
Note: Deflector area!
If drainage is to take place directly
from a line, it is advisable to arrange
the piping so that the air flow is diverted.
BEKOMAT 13, 13 CO, 13 CO PN25, 13 CO PN40
english

Advertisement

loading

This manual is also suitable for:

Bekomat 13 co pn25Bekomat 13Bekomat 13 co pn40