Power distribution units
Power planning for an Flex System Enterprise Chassis is essential.
The Enterprise Chassis has a maximum of six power supplies installed. So, careful consideration must be
given to providing the best power-optimized source. Both N+N and N+1 configurations are supported for
maximum flexibility in power redundancy. Each AC power supply in the chassis has a 16A C20 three-pin
socket and can be fed by a C19 power cable, from a suitable supply.
The chassis has the ability to accommodate a maximum of six power supplies, so it is possible to balance
a three-phase power input into a single chassis or a group of chassis. The chassis power system is
designed for efficiency using data center power consisting of three-phase, 60A Delta 200 VAC (North
America) or three-phase 32A wye 380-415 VAC (international). The chassis can also be fed from single-
phase 200 - 240VAC supplies, if required.
For further details, see the Flex System Enterprise Chassis Power Requirements Guide , available from:
https://support.lenovo.com/documents/LNVO-POWINF
Table 15. Power distribution units
Part number
Description
Switched and monitored AC PDUs
46M4002
1U 9 C19/3 C13 Active Energy Manager DPI PDU
46M4003
1U 9 C19/3 C13 Active Energy Manager 60A 3 Phase PDU
46M4167
1U 9 C19/3 C13 Switched and Monitored 30A 3 Phase PDU
46M4134
0U 12 C19/12 C13 Switched and Monitored 50A 3 Phase PDU
46M4140
0U 12 C19/12 C13 50A 3 Phase PDU
Enterprise AC PDUs
71762MX
Ultra Density Enterprise PDU C19 PDU+ (WW)
71762NX
Ultra Density Enterprise PDU C19 PDU (WW)
71763MU
Ultra Density Enterprise PDU C19 3 phase 60A PDU+ (NA)
71763NU
Ultra Density Enterprise PDU C19 3 phase 60A PDU (NA)
39Y8923
DPI 60A Three Phase C19 Enterprise PDU with IEC309 3P+G (208 V) fixed line cord
39Y8948
DPI Single Phase C19 Enterprise PDU without line cord
Front-end AC PDUs
39Y8934
DPI 32amp/250V Front-end PDU with IEC 309 2P+Gnd connector
39Y8938
30amp/125V Front-end PDU with NEMA L5-30P connector
39Y8939
30amp/250V Front-end PDU with NEMA L6-30P connector
39Y8940
60amp/250V Front-end PDU with IEC 309 60A 2P+N+Gnd connector
DC PDUs
44T0966
1U Higher Voltage DC PDU (240V/380V)
Uninterruptible power supply units