Serial digital alarm communicator transmitter (dact)

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
Model FS-DACT
Serial Digital Alarm Communicator Transmitter (DACT)
The FS-DACT Digital Alarm Communicator Transmitter Board is an optional module for the FS-250 and
FS-250C Fire Alarm System Control Panels. The FS-DACT provides telephone line connections for
communication with a DACR (Digital Alarm Communicator Receiver). The FS-DACT Board is mounted
on the Main Board. The FS-DACT Board options are set through the control panel programming
sequence.
PARTS SUPPLIED
1
FS-DACT Board
4
Spacers, 1"
1
Keps Nut, #6-32
1
Instruction Sheet
FS-DACT MOUNTING for FS-250 OR FS-250C
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-699464-10 (v10-21-10)
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to working on
equipment.
Step 3.) Mount DACT Board as shown, using four spacers
to the Main Board.
NOTE: Check to see that the header and
connectors are mated properly.
Step 4.) Attach ground wire as shown, using the nearest
main board mounting screw as shown.
Step 5.) Attach conduit and run wires as required.
Step 6.) Connect wires to the fire alarm system control unit
as required.
Step 7.) Apply power to system.
Step 8.) Program for proper operation of functions.
a) Tech Level>>Outputs>Option Mods>DACT CFG
(Set DACT line and general configurations)
b) Tech Level>>Outputs>Option Mods>DACT ACCTS
(Set DACT account configurations)
c) Maint Level>>Disable/Enable>Outputs>DACT
>Enabled
NOTE: See Programmer's Manual (P/N 315-
049403[C]) for more details on programming.
Step 9.) Check for proper operation of functions.
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Advertisement

loading

Summary of Contents for Siemens FS-DACT

  • Page 1 Model FS-DACT Serial Digital Alarm Communicator Transmitter (DACT) The FS-DACT Digital Alarm Communicator Transmitter Board is an optional module for the FS-250 and FS-250C Fire Alarm System Control Panels. The FS-DACT provides telephone line connections for communication with a DACR (Digital Alarm Communicator Receiver). The FS-DACT Board is mounted on the Main Board.
  • Page 2 NOTE: If installed in Canada, the signal receiving centre must not share a common communication channel with the protected premises. A dedicated line must be installed for use only by the FS-DACT. FS-DACT FORMAT DESCRIPTION...
  • Page 3 FS-DACT EVENT CODES SIA DCS Ademco 1400 Hz or 1400 Hz or (8 or 20) Contact ID Event Type 2300HZ 2300HZ Fire Point Alarm FA tuvw 1 110 xyz Fire Point Alarm Restore (Through Reset) FH tuvw 3 110 xyz...
  • Page 4 REN’s, contact the telephone company to determine the maximum REN for the calling area. If the FS-DACT equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify you of the discontinuance as soon as possible.