Mounting And Wiring - Siemens UP 588 Product Information

Technical product information

Advertisement

Touch panel UP 588
Touch panel UP 588/11
Touch panel UP 588/21
Accessories: Design frame, anodised aluminium
Location and function of the conjunction-
and operating elements
The device connections as well as the learning button
and programming LED which are required for the com-
missioning stage are accessible at the back of the de-
vice. Diagram 1 shows the back of the device.
N L
A1
A5
Diagram 2: Location of the display and
operating elements
A1 Terminal compartment for the connection of the
power supply terminal
A2 Programming LED
A3 Learning button
A4 Bus terminal
A5 Latching
The connection of the bus cable is carried out via a
standard bus terminal which is inserted in the corre-
sponding terminal locator on the right-hand side of the
housing. The learning button and the programming LED
are located on the left next to the module slot for the
bus terminal. The terminal for the power supply is on
the left-hand side of the device. The terminal must be
withdrawn in order to connect the power supply cables.
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O.Box 10 09 53, D-93009 Regensburg
-
+
LED Prog.
A2
A3
A4
UP 588, 6 pages
© Siemens AG 2006
Subject to change without prior notice
Technical Product Information
A6
A6
for adjusting the contrast
The contrast of the display can be changed via potenti-
ometer. The contrast is optimally pre-set for operation
in most environments at the factory. Changes should be
made only for extreme conditions.

Mounting and wiring

General description
The device may only be installed in the flush-type box
that is supplied. For the cable entry into the flush-type
box, the bus cable must be inserted into the bottom left
opening (B3) and the power supply cable must be in-
serted into the opening on the right-hand side (B2). The
bus and power supply cable may not be fed through an
opening together into the flush-type box. Within the
box, the cable should be led so that a minimum distance
of 10mm is guaranteed between the bus and the power
supply cable.
B7
Diagram 3: Installation of the touch panel
Update: http://www.siemens.de/gamma
instabus EIB
April 2006
5WG1 588-2AB01
5WG1 588-2AB11
5WG1 588-2AB21
5WG1 588-8AB01
B1
B2
B3
B4
B5
B6
Technical Manual
2.3.1.4/3