WIRING
600V class (when input power supply is 575V)
Terminal
Applicable
Screw
Inverter Model
Size
FR-A760-00017-NA
M4
FR-A760-00040-NA
M4
FR-A760-00061-NA
M4
FR-A760-00120-NA
M4
FR-A760-00220-NA
M5
FR-A760-00330-NA
M6
FR-A760-00550-NA
M8
FR-A760-00840-NA
M8
FR-A760-01040-NA
M10
FR-A760-01310-NA
M10
FR-A760-01520-NA
M10
FR-A760-02210-NA M12(M10)
FR-A760-02550-NA M12(M10)
FR-A760-03040-NA M12(M10)
FR-A760-04020-NA M12(M10)
FR-A760-04960-NA M12(M10)
FR-A760-06630-NA M12(M10)
*1
The cables used should be 75°C (167°F) copper cables.
*2
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, a screw for earthing (grounding), and P/+ for option connection.
A screw for earthing (grounding) of the 02210 or more is indicated in ( ).
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
18
Crimping Terminal
Tightening
Torque
R/L1,
N·m
*2
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
2-4
2-4
1.5
3.5-4
2-4
2.5
5.5-5
5.5-5
4.4
14-6
14-6
7.8
22-8
22-8
7.8
38-8
38-8
14.7
60-10
60-10
14.7
60-10
60-10
14.7
60-10
60-10
24.5
80-12
80-12
24.5
100-12 100-12 125-12 38-10
24.5
125-12 125-12 150-12 60-10
24.5
2×80-12
2×80-12 2×100-12
24.5
2×125-12 2×125-12 2×150-12
24.5
2×200-12 2×200-12 2×250-12
HIV, etc. (mm
Earth
R/L1,
(Ground)
U, V, W
P/+, P1
S/L2,
T/L3
Cable
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
3.5-4
3.5-4
3.5
8-5
5.5-4
5.5
5.5
14-6
14-6
14
14
22-8
22-8
22
22
38-8
22-8
38
38
60-10 38-10
60
60
60-10 38-10
60
60
60-10 38-10
60
60
80-12 38-10
80
80
100
100
125
125
100-10 2×80 2×80 2×100
100-10 2×125 2×125 2×150
100-10 2×200 2×200 2×250
1000
Cable Sizes
*1
2
)
Earth
R/L1,
(Ground)
U, V, W
P/+, P1
S/L2,
T/L3
Cable
2
2
2
14
2
2
2
14
2
2
2
14
2
3.5
3.5
12
8
5.5
10
14
14
6
22
22
4
38
22
2
60
38
2
60
38
1/0
60
38
2/0
80
38
4/0
125
38
250
150
60
2×2/0 2×3/0 2×4/0
100
2×4/0 2×250 2×300
100
2×300 2×300 2×350
100
2×400 2×400 2×500
AWG
Earth
(Ground)
P/+, P1
Cable
14
14
14
14
14
14
14
14
14
14
10
12
10
8
10
6
4
6
4
2
4
2
1/0
4
2
1/0
1
1/0
2/0
1
2/0
3/0
1
250
300
1
300 2×2/0
1
1/0
4/0
300
300