Gfk-2949C - GE PACSystems RX3i User Manual

Iec 104 server module ic695eis001
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Appendix D. Device Profile
Definition of time outs
Parameter
Default value
t
30s
0
t
15s
1
t
10s
2
t
20s
3
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s
Maximum number of outstanding I format APDUs k and latest acknowledge APDUs (w)
Parameter
Default value
k
12 APDUs
w
8 APDUs
Maximum range of values k: 1 to 32767 (2
Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU (Recommendation: w should not
exceed two-thirds of k).
Portnumber
Parameter
Portnumber
Redundant connections
Configurable
84
Time-out of connection establishment
Time-out of send or test APDUs
Time-out for acknowledges in case of no data messages
t
< t
2
1
Time-out for sending test frames in case of a long idle
state
Maximum difference receive sequence number to send
state variable
Latest acknowledge after receiving w I-format APDUs
-1) APDUs, accuracy 1 APDU
15
Value
2404
Number N of redundancy group connections used
PACSystems RX3i Ethernet 104 Server Module User Manual
Remarks
Remarks
Remarks
In all cases
Selected value
Fixed
Fixed
Fixed
Fixed
Selected value
Fixed
Fixed

GFK-2949C

Advertisement