AIR TO WATER HEAT PUMP Installation Manual Monobloc Outdoor Unit Model name: RUA – CP1701H* RUA – CP2101H* * See next page for model naming convention English Installation Manual...
Page 2
Monobloc Outdoor Unit Installation Manual Model naming convention:- RUA - CP 170 ❑ ❑ ❑ Area Area Europe Europe Factory option: Coil Protection Factory option: Coil Protection Blank Blank No Coil Protection No Coil Protection Coil Protection Coil Protection Power Supply Power Supply 3 phase 380/415V 3 phase 380/415V...
Monobloc Outdoor Unit Installation Manual Please read this Installation Manual carefully before installing the Air to Water Heat Pump. • This Manual describes the installation method of the Monobloc outdoor unit. REFRIGERANT This Air to Water Heat Pump uses an HFC refrigerant (R410A) in order to prevent destruction of the ozone layer.
Monobloc Outdoor Unit Installation Manual 3.0 Preparation for Installation Parts required to connect this product (Common items) Category Part Specification Quantity Strainer (water filter)* 1.2mm mesh Drain cock For water charge Water piping Inlet: 1 1/4” ** or 1” *** Isolating ball valves Outlet: 1”...
Monobloc Outdoor Unit Installation Manual Options Description Application Comments Italcoat heat exchanger Heat exchanger fins pre-treated with polyurethane / protection epoxy Fixed speed hydronic module Fixed speed pump for high external pressure Factory with expansion tank applications fitted. Variable speed hydronic module Variable speed pump for medium external pressure See model with expansion tank...
Page 7
Monobloc Outdoor Unit Installation Manual Periodic inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information • Any intervention on the refrigerant circuit of this product should be performed in accordance with the applicable legislation.
Page 8
Monobloc Outdoor Unit Installation Manual Ensure regularly that the vibration levels remain acceptable and close to those at the initial unit start-up. • • When the unit is subjected to fire, safety devices prevent rupture due to over-pressure by releasing the refrigerant.
Monobloc Outdoor Unit Installation Manual 5.0 Example of Monobloc Outdoor Unit Installation 5.1 Standard installation with domestic hot water (DHW) production DHW-S Radiators (heating only) Unit #01 Fan Coil DHW-V Add EXP-T Heating or cooling floor 5.2 Standard installation with header / follower (3 x follower units) configuration CHWST Header 01 Follower 01 Follower 02 Follower 03...
Monobloc Outdoor Unit Installation Manual 6.0 Main Components of the ESTIA Monobloc Outdoor Unit...
Page 11
Monobloc Outdoor Unit Installation Manual 6.1 Water side legend Label Description Water Pump -Main water pump -primary loop (in Hydronic module option) Water High Pressure Safety Relief Valve (300 kPa) (in Hydronic module option) Flow Switch (standard) Water Filter (standard in Hydronic module option) -->...
Monobloc Outdoor Unit Installation Manual 7.0 ESTIA Monobloc Outdoor Unit Installation Cautions • Install the Monobloc outdoor unit in a location that meets the following conditions after the customer’s consent has been obtained: • A well ventilated location free from obstacles near the air intakes and air discharge • A location that is not exposed to rain or direct sunlight • A location that does not increase the operating noise or vibration of the outdoor unit • A location that does not produce any drainage problems from discharged water...
Page 13
Monobloc Outdoor Unit Installation Manual 7.1 Moving and Positioning the Unit 7.1.1 Moving the Unit: Do not remove the pallet or the packaging until the unit is in its final position. These units can be moved with a fork lift truck, as long as the forks are positioned in the right place and direction on the unit. The units can also be lifted with slings (refer to Figure 2 and 3).
Page 14
Monobloc Outdoor Unit Installation Manual 7.1.2 Positioning the Unit: In case of extra-high units the machine environment must permit easy access for maintenance operations. Always refer to the Dimensions and Clearances figure to confirm that there is adequate space for all connections and service operations.
Monobloc Outdoor Unit Installation Manual Water Connections WARNING • Install water pipes according to the regulations of respective countries. • Install water pipes in a freeze-free place. • Make sure that water pipes have sufficient pressure resistance. The setting value of the pressure relief valve is 0.3 MPa. (3 bar) CAUTION •...
Page 16
Monobloc Outdoor Unit Installation Manual The water supply must be analysed and appropriate filtering, treatment, control devices, shut-off and bleed valves and circuits built in, to prevent corrosion (example: damage to the protection of the tube surface if the fluid is polluted), fouling and deterioration of the pump fittings.
Page 17
Monobloc Outdoor Unit Installation Manual Insulate all pipework, after testing for leaks, both to reduce thermal leaks and to prevent condensation. • • Wrap the insulations with a demisting screen. If the external unit water pipes are in an area where the ambient temperature is likely to fall below 0°C, •...
Page 18
Monobloc Outdoor Unit Installation Manual 7.2.4 - Water connection on unit Water outlet Water inlet Connection RUA-CP1701H* RUA-CP2101H* Water connections (without hydronic module) Inlet diameter (BSP Gas) 1” 1” Outlet diameter (BSP Gas) 1” 1” Water connections (with hydronic module) Inlet diameter (BSP Gas) 1¼”...
Page 19
Monobloc Outdoor Unit Installation Manual 7.2.5 - Unit without hydronic kit option Typical diagram of the hydronic circuit without the hydronic module 7.2.6 - Unit with hydronic kit option Typical diagram of the hydronic circuit with the hydronic module...
Page 21
Monobloc Outdoor Unit Installation Manual 7.3 Hydronic module There are 3 hydronic options for the unit RUA – CP1701H*, RUA – CP2101H*: No Hydronic module 2 Hydronic module equipped with fixed speed single pump 3 Hydraulic module equipped with variable speed single pump (low available pressure) CAUTION: The use of the hydronic module on open loop is prohibited.
Page 22
Monobloc Outdoor Unit Installation Manual 7.4 Minimum water loop volume This volume is required to obtain temperature stability and precision:- Application RUA-CP 1701H* 2101H* Air Conditioning 52.2 65.1 Heating or DHW application 102.6 126.6 To achieve the minimum water volume, it may be necessary to add a storage tank to the circuit.This tank should be equipped with baffles to allow mixing of the fluid (water or brine).
Page 23
Monobloc Outdoor Unit Installation Manual 7.6 Water charging Fill the heating system with water until the system water pressure is 0.2MPa (2.0 bar g). Check all of the water side connections to ensure that all connections are watertight and that there is no water leakage. During the water filling air may be trapped in the heating system / pipework.
Page 24
Monobloc Outdoor Unit Installation Manual Plate heat exchanger pressure drop (including internal piping) Units without hydronic module Pressure drop for unit without hydronic module 17 and 21 kW (heat exchanger + internal piping) ① Legend: ② RUA-CP1701H* RUA-CP2101H* Data for fresh water at 20°C Water flow rate, l/s Available external static pressure Available external static pressure for unit with fixed speed hydronic module 17 and 21kW...
Monobloc Outdoor Unit Installation Manual Available external static pressure for 21kW unit with variable speed hydronic module ① Legend: ② Pump speed = 100% ③ Pump speed = 75% ④ Pump speed = 50% ⑤ Pump speed = 38% Pump speed = 25% Data for fresh water at 20°C Maximum flow rate reduced if glycol is used in the heating system...
Page 26
Monobloc Outdoor Unit Installation Manual 7.8 Electrical connections WARNING • Ensure electrical circuits are isolated before commencing the electrical installation. • The electrical installation must be completed by a qualified electrician. • The electrical installation must comply to all Local, National and International electrical installation regulations.
Page 27
Monobloc Outdoor Unit Installation Manual 7.8.2 Control Line Connection Water or Air temperature control ° Outdoor Air Temp (OAT) C Normal/Alarm Ext. Circulator (on/off) 4 Customized inputs Normal/Defrost Power limitation switch Off peak sitch Loadshed request switch Solar input switch DHW request switch from tank DHW priority switch Anti-legionella cycle request...
Page 28
Monobloc Outdoor Unit Installation Manual CAUTION After the unit has been commissioned, the power supply must only be disconnected for quick maintenance operations (one day maximum). For longer maintenance operations or when the unit is taken out of service and stored (e.g. during the winter or if the unit does not need to generate cooling) the power supply must be maintained to ensure supply to the electric heaters (compressor coil heater, unit frost protection).
Page 29
Monobloc Outdoor Unit Installation Manual 7.8.5 Output line specifications (dependant on parameter settings) Maximum Connection Description Designation Output Current Destination (TB X2) Main water pump (Fixed Speed) DO#01 230VAC (Relay) 5A * 30, 32 Additional water pump DO#03 230VAC (Relay) 5A * 29, 32 100mA Diverting Valve DO#06 230VAC (Triac) 19, 23...
Monobloc Outdoor Unit Installation Manual 7.8.7 Electrical connection to the Monobloc outdoor unit • Ensure electrical circuits are isolated before commencing work • Remove the side cover and the electrical box cover from the Monobloc outdoor unit • The electrical power cable, for the Monobloc outdoor unit, must be sized in accordance Local, National and International regulations.
Page 31
BACnet / LON Gateways: It is possible to connect the Toshiba Monobloc outdoor unit to either a BACnet or LON system network. These connections are possible by using a factory fitted gateway, as an optional accessory, and as such have to be...
Page 32
Monobloc Outdoor Unit Installation Manual 7.8.10 External electrical connections – digital inputs (5V) Off/On Switch (remote) Mode Cool/Heat (remote) Comfort/Eco (remote) Safety Input Switch Flow Switch (standard) Dry contact Customized Customized Customized Customized Ground Function Switch No DI Open DI Short DI#01 Operation OFF Operation ON...
Page 33
Monobloc Outdoor Unit Installation Manual 7.8.11 External electrical connections – analogue inputs (resistance) DHW Tank Temperature Sensor Chiller water System Temperature Sensor resistence, Outdoor Air Temperature Sensor Ground-Sensor Function Description Set Up Parameter AI#01 DHW cylinder temperature sensor P719 AI#02 Chiller water system temperature sensor AI#04 Outdoor air temperature sensor...
Page 34
Monobloc Outdoor Unit Installation Manual 3-Wire (SPST) • Ensure 230VAC is not applied to terminal 19 on TB X2 Neutral Neutral External electrical heater connection / boiler ON/OFF signal NOTE: • It is possible to include electric heaters in the hydraulic circuit to ensure heating in case of low OAT or heat pump failure • The installer is responsible for ensuring that the installation complies with the applicable legislation in terms of electrical and thermal safety...
Page 35
Monobloc Outdoor Unit Installation Manual Boiler ON/OFF DHW cylinder heater connection (optional) T> Tmax. Depending on the configuration, it is possible to control up to three electric heaters or three electric heat stages i) One electric heat stage with one customized discrete output: EH1 ii) Two electric heat stages with two customized discrete outputs: EH1 and EH2 iii) Three electric heat stages with two customized discrete outputs: EH1 and EH2 iv) Three electric heat stages* with three customized discrete outputs: EH1 and EH2 and EH3.
Page 36
Monobloc Outdoor Unit Installation Manual 7.8.14 External electrical connections – additional outside air temperature (OAT) sensor If the unit is unfavourably located, leading to incorrect reading of OAT, it is possible to install an additional outdoor air temperature sensor, located in an appropriate position. Follow the connection details as shown below. Use parameter P511 to configure the OAT sensor.
Monobloc Outdoor Unit Installation Manual 8.0 System configuration Internal parameters are software codes that can be adjusted to optimize the performance of the system depending on the installation and the customers’ requirements. There are 3 access levels for the system Parameters: 1.
Page 38
Monobloc Outdoor Unit Installation Manual Day of the week setting The current day starts flashing: If necessary, press the Down key or the Up key to change the day of the week. Press the Schedule key to confirm your selection and go to the next parameter. Time format setting Once the day of the week has been confirmed, set the time format.
Page 39
Monobloc Outdoor Unit Installation Manual For 24-hour format: Set the hour and press the Schedule key to confirm. Then, set minutes and press the Schedule key to confirm. To confirm all changes, press and hold the Schedule key for 2 seconds. 8.1.2 Second step of configuration: Parameter menu According to the application of unit, several parameters are to be configured to allow the correct operation of system.
Page 40
Monobloc Outdoor Unit Installation Manual To validate the password and access parameter configuration, press and hold the Mode key for 2 seconds. To navigate in the parameter menu a - First possibility - Press and hold the Up or Down key. Select the Parameter Number with the Up or Down key.
Page 41
Monobloc Outdoor Unit Installation Manual 8.2 Parameter setting list Step Parameter Description Para No. Range Default User Configuration Codes User interface type: Selects type of user interface connected to the system: 0 = No user interface (RC will not initiate communication) 1 = Remote control by contacts 0 ~ 3 2 = RC remotely installed in the house (Air setpoint) 3 = RC remotely installed in the house (Water setpoint)
Page 42
Monobloc Outdoor Unit Installation Manual Step Parameter Description Para No. Range Default Compressor Configuration Codes Power limitation value: Compressor The compressor frequency is limited to this percentage of the maximum allowed frequency when 50 ~ 100 Configuration the Frequency Reduction Mode (P068) parameter [FREQ_RED] is set to “Yes” (LOADFACT). It can be activated with the power limitation switch.
Page 43
Monobloc Outdoor Unit Installation Manual Step Parameter Description Para No. Range Default Heat Minimum OAT (°C) -30 ~ 10 -7.0 Heat Maximum OAT (°C) 10 ~ 30 Heat Min Water Setpoint (°C) 20 ~ 40 Heat Max Water Setpoint (°C) 30 ~ 60 Cool Clim Curve Select: Climatic...
Page 44
Monobloc Outdoor Unit Installation Manual Step Parameter Description Para No. Range Default DHW Maximum Runtime If this parameter is configured to -1, maximum SHC or DHW Runtime is ignored. -1 (or 30) ~ Note: If SHC Maximum Runtime is set ([P705], it is also necessary to set DHW Maximum Runtime [P707].
Page 45
Monobloc Outdoor Unit Installation Manual Step Parameter Description Para No. Range Default Follower #2 Address: The address of the Follower unit. Please note that up to 3 0 ~ 239 follower units can be configured to operate in the same header / follower assembly Follower #3 Address: The address of the Follower unit.
Page 46
Monobloc Outdoor Unit Installation Manual 8.3 JBus Register Addresses Par. JBus Addr Mnemonic Description Range Unit JBus 0001H Outdoor Air Temperature 1/10°C RO/d RO/F 0002H Indoor Air Temperature 1/10°C RO/d RO/F 0003H Entering Water Temperature 1/10°C RO/F 0004H Leaving Water Temperature 1/10°C RO/F 0005H...
Page 47
Monobloc Outdoor Unit Installation Manual Par. JBus Addr Mnemonic Description Range Unit JBus 006DH CUST_DI8 Customized DI#8 Status 0/1 [Open/Close] RO/F 006EH RED_SW Power Limitation Switch 0/1 [Open/Close] RO/F 006FH OPEAK_SW Off Peak Hour Switch 0/1 [Open/Close] RO/F 0070H LSHED_SW Loadshed Request Switch 0/1 [Open/Close] RO/F...
Page 48
Monobloc Outdoor Unit Installation Manual Par. JBus Addr Mnemonic Description Range Unit JBus 01A7H htecooff Heat Away Offset (Air) -10.0 to 0.0 1/10 K 01A8H cloccstp Cool Home Setpoint (Air) 20.0 to 38.0 1/10°C 01A9H clunooff Cool Sleep Offset (Air) 0.0 to 10.0 1/10 K 01AAH...
Monobloc Outdoor Unit Installation Manual 9.0 Standard installations 9.1 Standard installation with booster electric heaters 9.1.1 Schematic #116 #116 Radiators (heating only) Unit #01 EH-Boiler OR Fan Coil Add EXP-T OR Heating / Cooling floor 9.1.2 Electrical connections Dry contact In resistance Triac Relay Ω...
Page 50
Monobloc Outdoor Unit Installation Manual 9.1.3 Control configuration steps Example Step Parameter Description Para No. Range Default Set Up Booster heater configuration: 0 = No backup 1 = Booster by 1 electric heater stage (EH1) 2 = Booster by 2 electric heater stage (EH1/EH2) 3 = Booster by 3 electric heater stages with 2 outputs (EH1/EH2) 4 = Booster by 3 electric heater stages with 3 outputs (EH1/EH2/EH3) 5~9 = No use for this configuration...
Page 51
Monobloc Outdoor Unit Installation Manual 9.2 Standard installation with DHW production 9.2.1 Schematic DHW-S #116 Radiators (heating only) Unit #01 Fan Coil DHW-V Add EXP-T Heating or cooling floor 9.2.2 Electrical connections Triac Relay Dry contact In resistance Out 230 VAC Out 230 VAC - 5 A Ω...
Page 52
Monobloc Outdoor Unit Installation Manual 9.2.3 Parameter configuration Para Example Step Parameter Description Range Default Set Up 3-way diveter valve selection: 0 = No DHW management 1 = Diverting valve 2 –points – NO contact (valve energized in DHW position) 2 = Diverting valve 2 –points – NC contact (valve de-energized in DHW position) 3 = Not used DHW cylinder sensor selection: Configuration...
Page 53
Monobloc Outdoor Unit Installation Manual Step Parameter Description Para No. Range Default Example Set Up DHW Cylinder ΔT (START): DHW mode is requested if the DHW cylinder water 2 ~ 10 temperature drops below the DHW set-point temperature (P406) minus the DHW cylinder ΔT (P721) (K) START / STOP Criteria for EWT ΔT (STOP): DHW mode is stopped if the EWT (of the Monobloc...
Page 54
Monobloc Outdoor Unit Installation Manual 9.3 Standard installation with DHW production and boiler 9.3.1 Schematic DHW-S #116 Radiators (heating only) Unit #01 Fan Coil DHW-V De-B add_pump Add EXP-T Heating or cooling floor 9.3.2 Electrical connections kW max. T> DHW-S Tmax. DHW-S DHW-EH Additional Power Limit.
Page 55
Monobloc Outdoor Unit Installation Manual 9.3.3 Parameter configuration Step Parameter Description Para No. Range Default Example Set Up DHW Mode Refer to “Installation with DHW Production” for DHW set-up Config. Back up type: Selects the type of boiler used on installation: 0 = No backup 0 ~ 9 9 = Backup by Oil or Gas boiler Boiler Config.
Page 57
Monobloc Outdoor Unit Installation Manual 9.4.3 Parameter configuration Step Figure Designation Description Range Default For header unit with a RC, to address the different units of header/follower installation, it is necessary to disconnect RS485 bus (Green connector J6) from Header and all Followers except the last one.
Page 58
Monobloc Outdoor Unit Installation Manual Step Figure Designation Description Range Default Apply procedure “Manage the Header and Follower units with a common user interface” to pass on Follower 1 status Allow the Header/Follower operation as Follower: Header / Follower 0 = Disable 0 ~ 2 selection 1 = Header...
Page 59
Monobloc Outdoor Unit Installation Manual Step Figure Designation Description Range Default To configure main pump of Follower 1 unit, the other units of installation must be in mode OFF (only Follower 1 unit is activated) Apply procedure “Manage the Header and Follower units with a common user interface” to pass on Follower 1 status 0 = No pump control 1 = Common Water Pump (a pump is installed outside of the unit on the water loop and is...
Page 60
Monobloc Outdoor Unit Installation Manual From this screen, it is possible to access all data of Follower 1 (parameter menu…). To finish the commissioning, it is necessary to configure the setpoint according to the user interface configuration Control Configuration for unit with remote user interface Step FC Description FC No.
Page 61
Monobloc Outdoor Unit Installation Manual Step FC Description FC No. Range Default Example Set Up Heat Climatic Curve Select: -1 = No Curve / Fixed Water Setpoint -1 ~ 12 0 = Custom Climatic Curve 1 to 12 = Heating Climatic Curve #number Heat Home Setpoint 20 ~ 60 Air setpoint for heating mode when Occupancy mode = Home (°C)
Page 62
Monobloc Outdoor Unit Installation Manual 9.6 Schematic Legend Label Symbol Designation Notes Device Field supplied Accessory Field mounted Option Factory mounted Field supplied Balancing valve Balancing to adjust the water flowrate Stop valve Field supplied Field supplied Automatic Air vent Automatic air vent(s) on highest position in the loop Field supplied Additional expansion tank depending the total water in...
Monobloc Outdoor Unit Installation Manual 10.0 Control overview 10.1 Operating modes Occupancy mode: Depending on unit configuration, the system can be controlled in two ways. The first possible method embraces the use of setpoints, where the outdoor air temperature has no effect on the temperature set by the control. The second control method is based on a climatic curve.
Page 64
Monobloc Outdoor Unit Installation Manual When Cooling mode is selected, the chiller or heat pump will operate in the Cooling mode in order to cool the water loop to the selected temperature. When the heat pump is in Heating mode, the heat pump heats the water loop to the selected temperature. When the outdoor air temperature is very low, electric heaters or boiler heating can be used in order to satisfy the heating demand.
Page 65
Monobloc Outdoor Unit Installation Manual 10.3.1 Predefined Climatic Curves: COOLING: If the cooling climatic curve [P586] is configured to “1” or “2”, the water setpoint will be calculated according to the selected cooling climatic curve. Two predefined cooling climatic curves are available: Climatic Curve Min.
Page 66
Monobloc Outdoor Unit Installation Manual • If OAT is invalid (not transmitted by the Inverter, out of range value, etc.), the Water Setpoint is equal to the current Max. Water Temp. • If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the current Min. Water Temp.
Page 67
Monobloc Outdoor Unit Installation Manual DHW only (setpoints defined below change also the setpoints for DHW mode): Water setpoint on Water setpoint on RC Occupancy Range Range RC direct access parameter menu DHW Setpoint 30 to 60°C DHW Setpoint [P406] 30 to 60°C DHW Anti Legionella DHW Anti-Legionella 50 to 60°C 50 to 60°C Setpoint Stp [P405]...
Page 68
Monobloc Outdoor Unit Installation Manual • If OAT is invalid, the Water Setpoint is equal to the Custom Max. Water Temp [P585]. • If OAT is above the current Maximum OAT threshold, the Water Setpoint is equal to the Custom Min. Water Temp [P584].
Page 69
Monobloc Outdoor Unit Installation Manual 10.4 Installation with remote user interface: When the unit is equipped with a remote user interface, the control can be based on the air setpoint. Depending on the occupancy and heating/cooling/DHW mode, the air setpoint is as given below. The air setpoint can be configured in two ways: • By direct access to the RC (refer to owner’s manual) • By access to the parameter menu via the RC or JBus / ModBus...
Page 70
Monobloc Outdoor Unit Installation Manual • The electric heaters are de-energized if OAT is above the AntiFreezeDeltaSetpoint* [P517] + 7.0 °C or if both EWT (if configured) and LWT are higher than AntiFreezeDeltaSetpoint* [P517] + 4.5 °C. • The electric heaters are energized if either alarm #50 or alarm #51 is active and can still automatically be reset * Modifying the pre-configured value is at the user’s responsibility.
Page 71
Monobloc Outdoor Unit Installation Manual • If trace heating is not used, or during a prolonged power failure, the unit water system must be drained to protect the unit • The heat exchanger temperature sensors are part of frost protection: If piping trace heaters are used, ensure the external heaters do not affect the measurement of these sensors CAUTION: Please note that “water freeze protection”...
Page 72
Monobloc Outdoor Unit Installation Manual 10.7.3 DHW electric heater: When the unit is requested to run in DHW mode, the DHW electric heater (if configured) can be used in order to provide domestic hot water.The discrete output can control a contactor (not supplied with unit). Contactor Coil: Characteristics 230 VAC...
Page 73
Monobloc Outdoor Unit Installation Manual 10.8 Pump configuration: There are a number of possible configurations of the hydraulic circuit: • Unit with hydronic module (internal main pump included) • Unit without hydronic module. An external pump is necessary • If a secondary hydraulic loop is used, this will have its own additional pump External main pump Additional pump Internal main pump (option)
Page 74
Monobloc Outdoor Unit Installation Manual 10.9 Electric Heaters: NOTE: The installer is responsible for ensuring that the installation complies with the applicable legislation in terms of electrical and thermal safety. It is possible to include electric heaters in the hydraulic circuit to ensure heating in case of low OATor heat pump failure.
Page 75
Monobloc Outdoor Unit Installation Manual 10.11 Coil heating control for compressor: CAUTION: When the unit doesn’t operate, the compressor can be energized. The coil heating control has the function of heating the compressor by applying a current to the compressor when not operating instead of using a case heater.
Monobloc Outdoor Unit Installation Manual 11.0 Start Up Before operating your system, for the first time, please complete the following checks: 1. Is there any shipping damage? 2. Unit is level in its installation 3. Power supply agrees with the unit name plate 4.
Page 77
Monobloc Outdoor Unit Installation Manual 11.2 Steps to clean, purge, and define a flow rate for hydraulic circuit With Variable Speed Hydronic With fixed speed hydronic With variable speed hydronic N° Without Hydronic Module Module module module T Adjustable constant speed Open the manual control valve fully (item 17) No manual control valve required Set the system pump * Read the BPHE pressure drop…...
Page 78
Monobloc Outdoor Unit Installation Manual 2. Available external static pressure for unit with fixed speed hydronic module 17 and 21kW Legend: RUA-CP1701H* RUA-CP2101H* Data for fresh water at 20°C Maximum flow rate reduced if glycol is used in the heating system Water flow rate, l/s 3.
Page 79
Monobloc Outdoor Unit Installation Manual 11.4 Actions in RC parameter menu or Service tools to activate the cleaning purge and control of flow rate for hydraulic circuit Steps Table Par. Designation Description Range Default Unit Quick Test Enable Access to Quick test mode 0 ~ 1 Water Pump Speed Activate the pump 0 ~ 100 QCK_TEST Cleaning procedure Wait around 2h that the hydronic circuit is cleaned Water Pump Speed Stop the pump...
Page 80
Monobloc Outdoor Unit Installation Manual 11.5 Commissioning modes: IMPORTANT: Field connection of interface circuits may lead to safety risks: any control box modification must maintain equipment conformity with local regulations. Precautions must be taken to prevent accidental electrical contact between circuits supplied by different sources: • The routing selection and/or conductor insulation characteristics must ensure dual electric insulation.
Page 81
Monobloc Outdoor Unit Installation Manual CAUTION: • Commissioning and start-up of the heat pump must be supervised by a qualified refrigeration qualified technician. • Start-up and operating tests must be carried out with a thermal load applied and water circulating in the water heat exchanger.
Monobloc Outdoor Unit Installation Manual 12.0 Maintenance Standard maintenance To ensure optimal efficiency and reliability of the units, we recommend establishing a maintenance contract with your local Service organisation. This contract will include regular inspections by Service specialists so that any malfunction is detected and corrected quickly, ensuring that no serious damage can occur.
Page 83
Monobloc Outdoor Unit Installation Manual Level 2 maintenance This level requires specific know-how in the electrical, hydronic and mechanical fields. The frequency of this maintenance level can be monthly or annually depending on the verification type. In these conditions, the following maintenance operations are recommended.
Page 84
Monobloc Outdoor Unit Installation Manual To reduce waste, the refrigerant and the oil must be transferred in accordance with applicable regulations, using methods that limit refrigerant leaks and pressure drops and with materials that are suitable for the products. Any detected leaks must be repaired immediately. The compressor oil that is recovered during maintenance contains refrigerant and must be treated accordingly.
Page 85
Monobloc Outdoor Unit Installation Manual Air heat exchanger We recommend, that finned coils are inspected regularly to check the degree of fouling. This depends on the environment where the unit is installed, and will be worse in urban and industrial installations and near trees that shed their leaves.
Page 86
Monobloc Outdoor Unit Installation Manual IMPORTANT: It is therefore not possible to optimise the refrigerant charge in the heating mode after a leak. The unit must be operated in the cooling mode to check, if an additional charge is required. Saturated temperatures based on the gauge pressure (in kPa g) Saturated Gauge pressure...
Monobloc Outdoor Unit Installation Manual 13.0 Sensor Temperature Monitoring Function Normally when the user interface will have the current indoor air temperature and the air set point displayed on the screen. If the system has been configured for water temperature control the user interface will have the current water temperature and the water set point displayed on the screen.
Monobloc Outdoor Unit Installation Manual 14.0 Troubleshooting Fault Symptoms: Symptom Possible Cause Corrective Action Incorrect remote controller setting Check remote controller operation and temperature setting Incorrect Parameter setting Check Parameter setting with the Parameter table. Room is not heated or cooled.
Page 89
Monobloc Outdoor Unit Installation Manual Check Code Diagnostic functional operation Determination and action Automatic Operational Cause Unit Status Reset Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error becomes Inverter discharge temperature Compressor stop definite after retrying operation 4 times. (TD) sensor failure 1.
Page 90
Monobloc Outdoor Unit Installation Manual Check Code Diagnostic functional operation Determination and action Automatic Operational Cause Unit Status Reset Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error becomes definite after retrying operation for 4 times. 1.
Page 91
Monobloc Outdoor Unit Installation Manual Check Code Diagnostic functional operation Determination and action Automatic Operational Cause Unit Status Reset Alarm reset by resetting the power supply to the Monobloc outdoor unit. Error becomes definite after retrying operation for 4 times. Discharge temperature too high Compressor stop 1.
Monobloc Outdoor Unit Installation Manual 15.0 Air to water heat pump operating conditions For proper performance, operate the air to water heat pump under the following temperature conditions: Cooling operation Minimum Maximum Outdoor temperature °C Entering Water temperature: °C Leaving Water temperature: °C Heating operation * Minimum...
Page 94
TOSHIBA CARRIER EUROPE S.A.S Route de Thil 01120 Montluel France 1402410101...