Technical data

This chapter contains the technical specifications of the du/dt filter and its
installation.
Input voltage (U
± 10%.
Ratings, weights and maximum cable sizes:
Filter type
Order code
U
(V)
N
I
(A)
N
L (microH)
Power loss (W)
Weight (kg, lb)
Maximum motor cable size in mm
Output connection size
Input connection size
Derating:
The load capacity (current and power) decreases if the installation site altitude
exceeds 1000 metres (3281 ft), or if the ambient temperature exceeds 40 °C
(104 °F).
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F), the rated output
current is decreased 1% for every additional 1 °C (1.8 °F). The output current is
calculated by multiplying the current given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100% -
%
1
°C
Maximum values table
Altitude derating
At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the derating is
1% for every 100 m (328 ft). For a more accurate derating, use the DriveSize PC
tool. The value calculated for the drive applies also to its du/dt filter.
): 380 ... 500 VAC 3-phase ± 10%, 380 ... 690 VAC 3-phase
1
· 10 °C = 90% or 0.90. The output current is then 0.90 · I
on page 12.
FOCH0320-50
68612209
500
445
22
520
65 (143)
2
3x(3x240)
M12
M12
FOCH0260-70
FOCH0610-70
68490308
68550505
690
289
35
370
47 (104)
65 (143)
3×(3×240)
3×(3×240)
M12
M10
. For I
thmax
thmax
Technical data
19
690
720
22
760
M12
M12
00096931 J
, see