6.2 Wiring with External Devices

(1) For voltage input
(2) For current input
*1
Use shielded twisted pair cables.
*2
Input resistors of the AJ65SBT2B-64AD
*3
For the current input, wire between the V+ and I+ terminals.
*4
If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 F
capacitor (25V or higher voltage-resistant product) between the V+ and COM
terminals.
*5
Ground the FG1 terminal without fail. If there is much noise, it may be better
to ground the AG terminal as well. If the grounding status of the AG terminal
is changed after the offset/gain values are set, set the values again.
*1
Utiliser des paires torsadées blindées.
*2
Résistances d'entrée du AJ65SBT2B-64AD
*3
Pour l'entrée de courant, raccordez entre les bornes V+ et I+.
*4
Si il y a un bruit ou des ondulations dans le câblage externe, connectez un
condensateur de 0,1 à 0,47 F (produit résistant à une tension de 25 V ou
plus) aux bornes d'entrée de l'appareil externe.
*5
Mettez la borne FG1 à la terre sans échouer. S'il y a trop de bruit, il peut être
préférable de mettre à la terre la borne AG également. Si l'état de mise à la
terre de la borne AG est modifié après le réglage des valeurs de décalage/
gain, définissez à nouveau les valeurs.
Signal source 0 to ±10VDC
*1 Shield
Signal source 0 to ±20mA
*1 Shield
Figure 6.1 Wiring with external devices
*4
CH1
V+
I+
COM
SLD
CH4
V+
*3
I+
COM
SLD
AG
*5
FG1
14
500k
250
500k
*2
500k
500k
250