Page 3
___________________ Introduction ___________________ Description ___________________ SENTRON Mounting ___________________ Connection 7KM measuring device Expansion module I(N), I(Diff), ___________________ analog Commissioning ___________________ Service and maintenance Manual ___________________ Technical data ___________________ Appendix 04/2017 L1V30408520AG-01...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Introduction ..............................7 Scope of delivery ........................7 Latest information ........................7 Description ............................... 11 Area of application ........................11 Performance features of the I(N), I(Diff), analog module ............11 Design ............................. 12 Mounting ..............................15 Warning ........................... 15 Installation location .........................
SIEMENS makes the OSS components of this product available to you at no extra cost. Insofar as SIEMENS has combined or linked certain components of the product with OSS components according to the definition of the applicable license, i.e. components that are licensed under GNU LGPL Version 2 or a later version and insofar as use of the relevant object file is subject to certain restrictions ("LGPL-licensed module"...
Page 8
The warranty obligations of SIEMENS are governed by the terms of the contract with SIEMENS. Modification of the product or the OSS components or use of them for a purpose other than the purpose specified by SIEMENS shall exclude them from the warranty in which case you will no longer have the right to technical support.
Page 9
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. The customer is responsible for preventing unauthorized access to its plants, systems, machines and networks.
Description Area of application The expansion module has been designed for use in combination with the 7KM PAC devices PAC3200 and PAC4200. The guidelines for the 7KM PAC devices also apply to the expansion modules. Performance features of the I(N), I(Diff), analog module The expansion module I(N), I(Diff), analog increases the scope of measuring functions of the PAC3200 / PAC4200 devices.
Description 2.3 Design Design Screw terminals for connection of current transformer or sensor Screw for mounting the expansion module I(N), I(Diff), analog Ventilation slot Diagnostic LED Figure 2-1 Schematic representation of expansion module I(N), I(Diff), analog connection: Current transformer connection for N-conductor current measurement 1 A / 5 A input connection: ●...
Page 13
Description 2.3 Design Diagnostic LED: The LED displays the module status: ● Green: Function and communication OK ● Red: Function or communication not OK Expansion module I(N), I(Diff), analog Manual, 04/2017, L1V30408520AG-01...
Mounting Warning WARNING Danger! High voltage Using devices when they are damaged may result in death, serious injury, or property damage! Do not install or start up damaged devices. Installation location The expansion module is inserted in the slot labeled "MOD1" or "MOD2" on the rear panel of the PAC3200 / PAC4200.
Page 16
Mounting 3.3 Installation steps CAUTION Electrostatic discharge The expansion modules contain electronic components that can be irreparably damaged by electrostatic discharge. When handling modules, make sure that all objects in the handling environment (persons, workstation and packaging) are properly grounded. Do not touch the module contacts. NOTICE Overheating of the device If the ventilation slots are covered, the expansion module can overheat.
Connection Safety information DANGER Danger! High voltage Failure to observe this notice will cause death, serious injury or property damage. Turn off and lock out all power supplying this device before working on it. Expansion module I(N), I(Diff), analog Manual, 04/2017, L1V30408520AG-01...
Page 18
Connection 4.1 Safety information WARNING Some of the following tasks are carried out when hazardous voltage is present. For this reason, they must only be carried out by qualified personnel who are familiar with and follow the safety regulations and precautions. Wear the prescribed protective clothing.
Connection 4.2 Connections Connections Terminal labeling Figure 4-1 Terminal labeling with screw terminals Number Terminal Function k↑ Current transformer input for N-conductor measurement l↓ Current transformer input for N-conductor measurement S1↑ Summation current transformer input; analog input I S2↓ Summation current transformer input; analog input I S1↑...
Page 20
Connection 4.2 Connections Example connections Several example connections for the expansion module I(N), I(Diff), analog can be found below. The device can be connected for current measurement and/or use of the analog inputs I or a combination of both. The module must be individually configured to meet the requirements of the application.
Page 21
Connection 4.2 Connections input: A suitable summation current transformer must be used to measure the PE current. The device input must be configured accordingly. Note When the expansion module is used as residual current monitor, the device is only designed to display the residual current.
Page 22
Connection 4.2 Connections Measurement of physical quantities via analog inputs I and I Figure 4-3 Possible connection type for measuring physical quantities The I and I analog inputs can also be used to measure analog signals (0 / 4 ... 20 mA). The device inputs must be configured accordingly.
Commissioning Overview Requirements 1. The expansion module has already been installed. 2. The expansion module and the PAC device have been connected up correctly. Note Check the connections! Failure to connect up the device correctly can result in malfunctions and failure of the device. Before you start commissioning the device, check that all connections are correct.
PAC device using the SENTRON "powerconfig" configuring software. The SENTRON powerconfig configuring software can be downloaded from the Industry Online Support website (https://support.industry.siemens.com/cs/ww/de/view/63452759). Setting parameters on the PAC device In the menu "EXPANSION MODULES", call the "I(N) I(DIFF) ANALOG" that you want to configure and then select menu item "SETTINGS".
Page 25
Commissioning 5.2 Setting the expansion module parameters The I and I inputs of the module can be configured in the "SETTINGS" menu. ► Set the I input parameters ► Set the I input parameters ► Set the I input parameters ◄...
Page 26
Commissioning 5.2 Setting the expansion module parameters Setting the ADC 0 - 20 mA parameters LOWER LIMIT 0 – 9999 (specification of lower limit) NEGATIVE ON/OFF (in the ON position, the lower limit is signed as a negative number) UPPER LIMIT 0 –...
PAC device using the SENTRON powerconfig configuring software. The SENTRON powerconfig configuring software can be downloaded from the Industry Online Support website (https://support.industry.siemens.com/cs/ww/de/view/63452759). Reading out from PAC device In the menu "EXPANSION MODULES", call the "I(N) I(DIFF) ANALOG" from which you want to read measured values and then select menu item "MEASUREMENT".
Service and maintenance Calibration The device has been calibrated by the manufacturer before shipping. Recalibration is not required provided the environmental conditions are maintained. Firmware update The expansion module I(N), I(Diff) analog supports firmware updates. Use the latest version of the SENTRON powerconfig software to install updates. For update instructions, please see the related documentation and online help.
Procedure Note Loss of warranty If you open the device, you will invalidate the Siemens warranty. Return faulty or damaged devices to Siemens. If the device is faulty or damaged, proceed as follows (only during the warranty period): 1. Uninstall the device.
Technical data Technical specifications Device configuration ● I - measuring input ● I - analog input ● I - analog input Supply voltage No external supply voltage is required. The expansion module is supplied via the PAC device. Measuring inputs Connection to AC power systems is only possible via external current transformers.
Page 32
Technical data 7.1 Technical specifications Measuring accuracy Class 1 according to EN61557-12 Measurement of residual currents according to IEC / TR 60755, type Annex B When measured by external current transformers, the accuracy of the measurement depends on the quality of the transformers. Connection elements Table 7- 1 Conductor cross-section...
Page 33
Technical data 7.1 Technical specifications Dimensions and weight Enclosure dimensions (inserted in PAC device) W x H x D 43 mm x 63 mm x 34 mm Enclosure dimensions (not inserted in PAC device) W x H x D 43 mm x 63 mm x 42 mm Weight Device without packaging 58 g...
Page 34
SENTRON PAC measuring device. You can find more information in the operating instructions and manual for the SENTRON PAC 3200 (https://support.industry.siemens.com/cs/document/26504150/manual-sentron-power- monitoring-device-pac3200?dti=0&lc=en-WW) or PAC 4200 (https://support.industry.siemens.com/cs/document/34261595/sentron-pac4200-power- monitoring-device-system-manual?dti=0&lc=en-WW) Power Monitoring Device.
Read Write; read and write access Offset Offset Number of Name Format Unit Value Access (MOD1) (MOD2) registers range 58001 58123 Float 58003 58125 Float 58005 58127 Float See also PAC RS485 expansion module (https://support.industry.siemens.com/cs/document/28865965/manual-sentron-expansion- module-pac-rs485?dti=0&lc=en-WW) Expansion module I(N), I(Diff), analog Manual, 04/2017, L1V30408520AG-01...
Index IN connection Design, (Description) Installation location Installation, 15 Ambient conditions Installation steps Technical specifications, 34 Installation, 15 Approvals Technical specifications, 34 Latest information Introduction, 7 Calibration Service and maintenance, 29 Connection elements Technical specifications, 32 Measuring accuracy Technical specifications, 32 Measuring inputs Technical specifications, 31 Degree of protection and protection class...
Page 38
Index Setting the I5 input parameters Setting the expansion module parameters, (Commissioning) Setting the IN input parameters Setting the expansion module parameters, (Commissioning) Supply voltage Technical specifications, 31 Terminal labeling Connections, (Connection) Third-party software Introduction, 7 Troubleshooting guide Service and maintenance, 29 Warranty Service and maintenance, 30 Expansion module I(N), I(Diff), analog...