LG PRDCA0 Installation Manual page 22

Ahu communication kit
Table of Contents

Advertisement

COMMUNICATION KIT INSTALLATION
22
• Dip S/W(SW03) NO 4 : ON
Analog Input 10-4 (VDC)
Normal
0.5
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9.5
Example) 5.85~6.15 Voltage is recognized as 6.0V.
!
CAUTION
If you want to control the Room Temperature using Remote controller, you have to be off
the Dip S/W 4 and Dip S/W 6, and setting the Rotary S/W to the '0' .
Range
Min.
Max.
0
1.15
1.35
1.65
1.85
2.15
2.35
2.65
2.85
3.15
3.35
3.65
3.85
4.15
4.35
4.65
4.85
5.15
5.35
5.65
5.85
6.15
6.35
6.65
6.85
7.15
7.35
7.65
7.85
8.15
8.35
8.65
8.85
10
Room Temp.(°C)
Cooling
Not available
18
18
18
19
20
21
22
23
24
25
26
27
28
29
30
Not available
Room Temp.(°C)
Heating
Not available
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Not available