Akr series, low voltage power circuit breaker
Table of Contents

Advertisement

Type AKR Breakers Tri p Devices
MicroVersaTrip
RMS-9 Tripping Functions
R
Current Setting (Standard)
The adjustable current
setting determines the
nominal long time current
setting with a
±
1 0% band
width . With a 1 . 1 setting the
breaker will carry indefinitely
without tripping the rating
plug rating . Changing the
setting changes the norminal
current rating for the breaker.
Long-Tim e Delay (Standard)
This long-time delay adjust­
ment varies the time it will
take the breaker to trip under
sustained overload condi­
tions. It provides the function
of withstanding momentary
overloads such as motor
starting, welding, or other
overcurrent conditions with­
out interrupting the service.
Long-Time
Light (Standard)
Pickup
The long-time pickup light
provides visual indication
that the breaker is experi-
encing an overload condi-
tion. Indication is provided
by a light-emitting diode
(LED) which is only activated
prior to trip-out and during
long-time time-out. Saves
test and system start up time.
S hort-Time
(Optional)
Pickup
This short-time picKup
adjustment controls the level
of high current the breaker
can carry for short periods of
time without tripping. Per-
mits downstream breakers
to clear short circuit faults
without tripping out the
upstream protective device.
18
CURRENT SETTING
1.1X
SETTING( C)
LONG TIME DELAY
2
3
, � .
DELAY
RATING PLUG
CAT. NO. TR20S2000
0
TEST
x�2ooo A
S�2000A
PICKUP
PICKUP
®
SHORT TIME PICKUP
2.5C
3C
2C
C
1.5C
SC
7C
9C
SHORT-TIME
PICKUP