Huawei UPS2000-G-2KRTL User Manual

Huawei UPS2000-G-2KRTL User Manual

Ups2000-g series
Hide thumbs Also See for UPS2000-G-2KRTL:

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Issue
08
Date
2017-08-04
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS2000-G-2KRTL

  • Page 1 UPS2000-G-(1 kVA-3 kVA) User Manual Issue Date 2017-08-04 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    The symbols that may be found in this document are defined as follows. Symbol Conventions Symbol Description Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Updated the display of battery power backup time. Issue 05 (2016-01-25)  Updated 06: Set the battery capacity and 07: Set the discharge time limit in 4.5 Setting Parameters.  Added bypass overload capability Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 5 Added button functions for exiting parameter setting screens and alarm screen. Issue 03 (2015-10-20) Updated the button description. Issue 02 (2015-08-29) Updated the routine maintenance. Issue 01 (2015-06-25) This issue is the first official release. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 6: Table Of Contents

    4.7 Alarm Handing................................36 4.8 Alarm Indication ................................. 47 5 Operations ............................ 48 5.1 Checking Before Powering On the UPS ........................48 5.2 Starting the UPS ................................. 48 Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 7 9.6 Battery Specifications ..............................66 9.7 ECO Feature ................................68 9.8 System Electrical Specifications ..........................68 9.9 Safety Regulations and EMC ............................69 A Acronyms and Abbreviations ....................70 Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 8: Precautions

    Strictly obey the operating environmental requirements specified in related use manuals when using or storing the device. Donnot places the UPS in the following environments: Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Installation

     To completely disconnect the UPS, shut down the UPS and then unplug the power cable.  Prevent liquid or any other foreign objects entering the UPS. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 10: Servicing, Maintenance, And Troubleshooting

    UPS2000-G-(1 kVA-3 kVA) User Manual 1 Precautions 1.6 Servicing, Maintenance, and Troubleshooting Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 11: Overview

    The two models are represented by 3 kVA UPS2000-G-3KRTS model-rack in the description of their common features mounted-IEC and parameters. UPS2000-G-3KRTL 3 K-long backup time model-rack mounted-IEC Figure 2-1 shows the UPS model number. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Working Principle

     L: long backup time model. You need to use an external large-capacity battery pack 2.2 Working Principle Figure 2-2 shows the UPS conceptual diagram. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Product Structure

    (1) Mains input socket (C14) (2) Input circuit breaker (3) Universal serial bus (USB) port (security (4) RS232 port protection mechanism supported) (5) Optional card slot (6) Output socket (C13) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 14 (1) Mains input socket (C14) (2) Input circuit breaker (3) USB port (security protection (4) RS232 port mechanism supported) (5) Optional card slot (6) Output socket (C13) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 15 UPS2000-G-(1 kVA-3 kVA) User Manual 2 Overview Figure 2-6 Rear view of UPS2000-G-2KRTL (1) Mains input socket (C14) (2) Input circuit breaker (3) USB port (security protection mechanism (4) RS232 port supported) (5) Optional card slot (6) Output socket (C13)
  • Page 16: Optional Components

    Applicable to the string with eight 9 3 kVA UPS with Ah/12 V DC batteries. long backup The output voltage of time. the battery pack is 96 V Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 17 UPS to prevent the abnormally high voltage from flowing into the UPS and damaging the UPS. In addition, the OVCD provides extra input surge voltage absorbing Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 18 User Manual 2 Overview Optional Model Function Remarks Component capability and input filtering capability. Guide rail None Secures the UPS or Configured in component battery pack. rack-mounted scenarios. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 19: Installing The Ups

    Reserve a clearance of at least 500 mm respectively from the front and rear panels of the UPS to the wall or adjacent equipment to facilitate ventilation and heat dissipation, as shown in Figure 3-1. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Tools

    Clamp meter Multimeter Labels Phillips screwdriver (PH2 x 150 mm or PH3 x 250 mm) Flat-head Torque screwdriver Crimping tool Diagonal pliers screwdriver (2 mm x 80 mm) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Installing Ups

    Step 2 Install guide (2 U) on the Cabinet. Then Place the UPS on the guide rails. For details about how to install guide and UPS on the cabinet, see the UPS2000-G-(1 kVA-3 kVA) Rail Assembly Quick Installation Guide. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 22 Step 5 Place UPS on the support bases in sequence. Step 6 Adjust the UPS and the support bases to be horizontally. Figure 3-3 Tower-mounting the UPS Figure 3-4 Tower-mounting the UPS Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Installing Cables

    Figure 3-5 Connecting cables to the 1KRTS UPS output Figure 3-6 Connecting cables to the 1KRTL UPS output Figure 3-7 Connecting cables to the 2KRTS UPS output Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 24 The installation method for 1 kVA UPS, 2 kVA UPS, and 3 kVA UPS are the same. The figures below are based on the 3 kVA UPS. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 25 UPS, and 3 kVA UPS are the same. The figures below based on the 3 kVA UPS. Figure 3-12 Installing an optional card on the 3KRTS UPS Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 26 The USB channel supports a serial data communications protocol between the UPS and the PC.  If you connect a DB9 connector to the RS232 port, the UPS can communicate with the PC over serial data. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 27 Figure 3-16 Connecting cables to the 1KRTS UPS input Figure 3-17 Connecting cables to the 1KRTL UPS input Figure 3-18 Connecting cables to the 2KRTS UPS input Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Installation Verification

    Cable routing meets engineering requirements. Power cables and battery cables are tightened to Cable connections specified torques using a torque wrench, connected correctly, and free of damage. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 29 1 ohm. Distances between cable Distances between cable ties are the same, and no burr ties exists. Operating environment Clean the conductive air and other sundries. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Setting Control Panel

    Figure 4-1 LCD panel Table 4-1 Icon description Icon Function Backup time information Alternately displays the remaining power backup time, alarm ID , and CF (only displays in frequency conversion Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 31 Indicates that batteries are supplying power. Indicates that batteries are being charged. Displays that the UPS is in bypass mode. Displays that the UPS is in ECO mode. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 32: Buzzer Alarm Tones

    Beeps once every 4 seconds. Minor alarm Beeps once every second. Overload Beeps twice every second. Critical alarm Buzzes continuously. Bypass mode Beeps once every 10 seconds. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Character Display

    ECO mode High voltage Low voltage Constant-frequency mode Buzzer off Automatic startup Dynamic Host Configuration Protocol (DHCP) IP ADS IP address SUB NET Subnet mask GAT UAY Gateway Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Buttons

    Transferring to battery self-check: In normal mode, ECO mode, or frequency conversion mode, hold down ON/MUTE for more than 5 seconds to enter the battery self-check test. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Setting Parameters

    5 seconds to enter the alarm cause ID screen. Press ON/MUTE to view the previous option. Press SELECT to view the next option. 4.5 Setting Parameters Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 36 UPS2000V200R001C01SPC300 (V2R1C1SPC30 is displayed on the NetEco; you can query the version information by choosing Maintenance > Current Version). The UI snapshots are subject to change without notice. Contact Huawei technical support to obtain the latest snapshots if necessary. There are seventeen configurable parameters on the LCD. The following figures show the parameter setting screens.
  • Page 37 Enable or disable the bypass function. ENA: Enables the bypass mode. DIS: Disables the bypass mode (default value).  Set the highest input voltage in bypass mode. Display Setting Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 38 9 Ah and not configurable. The default value for long backup time model is 18 Ah.)  Set the discharge time limit. Display Setting Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 39 13–24: Set the parameter based on the preset output voltage. The value range is –13 V AC to –24 V AC. (The default value is –22 V AC.) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 40 IP address, subnet mask, and gateway need to be set on the WebUI of the SNMP card. For details, see RMS-SNMP01B SNMP Card User Manual.  DHCP function setting Display Remarks Address allocation mode setting: ENA: enabled DIS: disabled (default value) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 Press ▲ or ▼ to switch between different screens. On the ESC screen, press OFF/ENTER to exit. (The default value is 192.168.0.1.)  No battery alarm disabled setting Display Remarks Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 42: Operating Modes

    AC output current, while charging batteries. ECO mode When the input voltage is in the preset range, the UPS transfers to bypass mode to save energy. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 43: Alarm Handing

    Table 4-6 Alarms Alar Alar Alar Alarm Alarm Clear Trigger Impact on Repair Proposal m ID Severity Mode Condition the System Cause Name Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 44 UPS.  Possible cause: An internal fault has occurred. Measure: Contact the dealer or Huawei technical support. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 45  If battery  Possible cause: packs are The charger is connecte abnormal. d before Measure: Check that the charger startup, voltage is the UPS normal Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 46  If battery  Possible cause: packs are The mains is connecte abnormal, and d before the batteries are overdischarged. startup, Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 47 5 state and Measure: V, or is cannot start. Contact the higher than dealer or 15 V (when Huawei the UPS is technical not started). support to Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 48 Measure: Check that the load types are supported by the UPS.  Possible cause: The hardware is Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 49 UPS, the Huawei technical voltage. support. transfers to bypass mode. Interna Critical This alarm The inverter If this alarm Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 50 Interna This alarm If this alarm  Possible cause: Critical l fault must be difference is generated The hardware is manually between the during the damaged. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 51 Huawei technical support. Interna Minor This alarm is The charger The power Possible cause: The l fault automatically has no output. supply from internal connection Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 52 Measure: Lower the exceeds output load or replace the the rated mode. UPS with a UPS load.  If the with a larger  In normal capacity. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 53 Measure: Reduce the load or replace the UPS with a UPS with a larger Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Alarm Indication

    Alarm Display (Blinking) Buzzer Insufficient battery capacity Beeps once every second. Overload Beeps twice every second. Battery disconnection Beeps once every second. Overcharge Beeps once every second. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Operations

    UPS powers on). The battery voltage range is (Number of batteries x 10.8) to (Number of batteries x 14) V DC. 5.2 Starting the UPS Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 56 Step 1 After power on the UPS, it enters standby mode, as shown in Figure 5-1. Hold down the SELECT button for 5 seconds. The UPS enters the preset mode. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 57 18 Ah to 999 Ah. Figure 5-4 Setting the battery capacity Step 5 Start the UPS to inverter mode. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Shutting Down The Ups

    5.6 Transferring to Battery Self-check In normal mode, ECO mode, or frequency conversion mode, hold down ON/MUTE for more than 5 seconds to enter the battery self-check test. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 59: Enabling Or Disabling The Buzzer

    Hold down SELECT and OFF/ENTER both for 5 seconds to enter the alarm cause ID screen. Press ON/MUTE to view the previous option. Press SELECT to view the next option. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Maintenance And Storage

    Table 6-1 UPS charging during storage Storage Temperature Charge Interval Charge Duration –25° C to +40° C Three months 1–2 hours 40° C to 45° C Two months 1–2 hours Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Routine Maintenance

    If an alarm is Monthly are operating present, rectify the properly by fault by checking the observing the status device status and icons on the LCD, parameters. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 62: Battery Maintenance

    When moving batteries, avoid handling the battery upside down, handle batteries gently, and pay attention to personal safety.  Keep the battery switch off when installing or maintaining the batteries. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 63 5. Batteries are not deformed or bulged. 1. The ambient 1. Identify the Battery operating Monthly battery cause of the temperature temperature is abnormal battery 25± 5° C. operating Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 64 The difference Quarterly temperature sensor measurement between the sensor in the accuracy temperature correct position. measured by the temperature sensor 2. Replace the and the temperature battery Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 65 (recommended) discharge test when exception is the UPS is backed identified. up to verify that the batteries can 2. If the fault persists, contact Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 66 (A torque wrench is used for checking the torque. After checking that the battery screws meet the requirements, mark the screws for later check.) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 67: Troubleshooting

    5 hours and then check the in specifications. battery capacity. If the battery capacity is still insufficient, contact the dealer or Huawei technical support. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 68 UPS2000-G-(1 kVA-3 kVA) User Manual 8 Troubleshooting Symptom Possible Cause Measures Batteries are faulty. Contact the dealer or Huawei technical support to replace batteries. Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Specifications

    Altitude < 1000 m –40° C to +70° C (battery pack: –20° C to +40° C) Storage and transportation temperature Noise < 50 dBA @ 1 m Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Mains Input Electrical Specifications

    290 V AC (tolerance ± 5%, load percentage < 80%) hest  270 V AC (tolerance ± 5%, 80% < load percentage < 100%) reco very volt Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 71: Bypass Input Electrical Specifications

    9.5 Output Electrical Specifications Table 9-5 Output electrical specifications Item 1 kVA 2 kVA 3 kVA Rated capacity 1000 VA/800 2000 VA/1600 3000 VA/2400 Output power factor (PF) Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 72 (in line mode) after 0.5 seconds max. Dynamic voltage tolerance ± 5% ± 5% Average frequency tracking rate 1 Hz/s Transfer time Transferring from normal mode to battery mode Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 73: Battery Specifications

    Standard > 4 minutes (at full rated load) p time model Long Depending on the capacity of external batteries, for details, see Table backup 9-9. time model Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 74 47.0 25.0 25.0 83.0 45.0 45.0 159.0 85.0 85.0 3 Battery 39.0 27.0 groups 55.0 40.0 95.0 70.0 175.0 130.0 4 Battery 63.0 39.0 groups 87.0 55.0 Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 75: Eco Feature

    9.8 System Electrical Specifications Table 9-9 System Electrical Specifications Item 1 kVA 2 kVA 3 kVA Number of UPSs Cannot support connected in parallel System efficiency Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Safety Regulations And Emc

    Power magnetic IEC 61000-4-8 susceptibility (PMS) Harmonic current IEC61000-3-12 Flashing IEC61000-3-11 (input current > 16 A) Impact current (lightning  IEC/EN60240-2 protection)  IEC/EN61000-4-5  YD/T1095-2000  YD/T944-2007 Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 77: A Acronyms And Abbreviations

    EEPROM HTTP HTTP-Hypertext Transfer Protocol liquid crystal display power factor correction Recommend Standard 232 RS232 Simple Network Management Protocol SNMP THDv total harmonic distortion voltage Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 78 UPS2000-G-(1 kVA-3 kVA) User Manual A Acronyms and Abbreviations uninterruptible power system Issue 08 (2017-08-04) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.