10
en | Connection of the Devices
Warning!
Risk of electric shock!
!
Disconnect the mains supply voltage before doing any work at
the devices inside the enclosure.
Notice!
All cables connected to the AMC modules and the power supply
are classified as Class 2 Conductors, with the exception of the
battery cable and the AC input cable. These two are non-power
limited circuits.
Notice!
For UL installations a minimum of ¼" (6.4 mm) spacing is to be
maintained between all class 2 or 3 conductors and all electric,
light, power, Class 1 conductors, non-Class 2 or 3 signaling
conductors, or medium-power network-powered broadband
communications-circuit conductors (see areas 3 and 4 in Fig.
3.1).
Mounting Components
1.
2.
The components described below refer to Cable A (Figure 1.2):
Cable A - AMC Power Cable
1.
2.
3.
2018-04 | AEC-AMC2-UL1 |
Mount the AMC on the rail on the right (item 2 – Fig. 1.1)
and left aside the power supply.
If rechargeable batteries are used, put them on the bottom
of the housing and secure them using clip 7 (Fig. 1.1).
Connect the 7-pin plug A1 to the AMC's power supply
connector (labeled: POWER).
Attach connectors A3 to the PS-interface DC and A2 to the
interface labeled OK.
Connect the grounding cable A4 at the grounding point 3
(Fig. 1.1).
AMC2 enclosure - 1 DIN
Bosch Access Systems GmbH