GE PACSystems RX3i User Manual page 10

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

10
GFK-2748C
Update rate = 100 ms or the PLC scan rate (whichever is longer)
Timing AB – AllGridAlarmsOK follows the timing of the alarm that causes it to be cleared or set.
LEDs
LED
RUN
FLT
GRID 1
GRID 2
State
Green
The module is operating correctly and communicating with the RX3i.
Red
The module is operating without backplane communication.
Off
The module is not operating.
Green, blinking
During the period when GREEN is ON, Grid 1 can be connected to Grid 2.
Green, steady
Grid 1 and Grid 2 are connected.
Red
The module has detected a fault condition.
Off
The module has not detected a fault and the grids are not synchronized.
Green
Indicates a voltage signal has been detected on Grid 1.
Red
A frequency out-of-range condition has been detected on Grid 1.
Off
No zero crossing signal of Grid 1 has been detected during the last 250 ms
time period.
Green
Indicates a voltage signal has been detected on Grid 2
Red
A frequency out-of-range condition has been detected on Grid 2.
Off
No zero crossing signal of Grid 2 has been detected during the last 250 ms
time period.
RX3i Power Sync and Measurement System
Definition

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ic694psm001-abIc694acc200-a

Table of Contents