Installation Instructions
Model PAL-1
Parallel Printer
Operation
The model PAL-1 from Siemens Industry, Inc. allows the connec-
tion of an ITE Centronics parallel printer to the Siemens FireFinder-
XLS, MXL, FireFinder-NCC, FC2025, FC2050, FC922, FC924,
Desigo CC and Cerberus DMS systems. See the manufacturer's
installation manual for self diagnostics.
The PAL-1 printer can be used with control panel models XLS,
FC2025, FC2050, FC922, FC924, NCC, Desigo CC, and Cerberus DMS
Management Systems in UL864 and ULC-S527 installations. The PAL-1
printer can be used in UL2572 installations, Control and Communication Units for Mass Notification. For
supplementary use only, the NCC and PAL-1 may be connected to the UL1076 approved XLS and MXL
control panels.
Installation
UPS Standby Power
The PAL-1 printer requires a standby power source in the event of the loss of primary input power (AC
mains). Refer to Figure 2 for the connection of a UPS to meet this requirement.
TO TRI-60/B6/S OR HTRI-S/-D/-R INPUT
TERMINALS. PROGRAM AS NORMALLY OPEN
TROUBLE CAUSING INPUT IN CSG-M (AccuLINK)
OR ZEUS AND FPI-32 OR DPU, AS APPLICABLE.
REFER TO TRI-60 INSTALLATION INSTRUCTIONS,
P/N 315-092329, THE TRI-B6 INSTALLATION
INSTRUCTIONS, P/N 315-093315,
INSTALLATION INSTRUCTIONS, P/N 315-096242 OR
315-049481,
INSTRUCTIONS, P/N 315-033300 OR 315-049075,
TERMINAL BLOCK
LOCATED ON
UPS SYSTEM
CONTROL BOARD
NOTES:
1. All wires 14 AWG min, 600V insulation.
2. Wiring to the printer and must be 14 AWG min., 600V insulation in conduit, and located in the same room as the
control panel.
3. Use the UPS ICS Lifeline Model 9300057.
4. Standby Power requirements: 120 VAC, 3A for 24 hours.
Siemens Industry, Inc.
Building Technologies Division
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-092408-14
120 VAC
OR THE TRI-S
UTILITY
POWER
OR THE HTRI-S/-D/-R INSTALLATION
SOURCE
AS APPLICABLE.
1
2
3
4
5
6
NO
C
NC
NO
C
NC
1
H
AC
BATTERY
INPUT
FAIL
FAIL
120 VAC
UTILITY INPUT
POWER
Figure 2
UPS Wiring Diagram
POWER TO
PRINTER
DO NOT
120 VAC
USE
SEE NOTE 4
2
3
4
5
6
7
8
GND
N
H
N
H
GND
N
120 VAC
120 VAC
OUTPUT OF
INPUT
POWER
THE UPS
AFTER FILTER
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
1
Figure 1
PAL-1 Printer
DO NOT
USE
9
10
11
H
GND
N

Advertisement

loading

Summary of Contents for Siemens PAL-1

  • Page 1 Installation UPS Standby Power The PAL-1 printer requires a standby power source in the event of the loss of primary input power (AC mains). Refer to Figure 2 for the connection of a UPS to meet this requirement. TO TRI-60/B6/S OR HTRI-S/-D/-R INPUT TERMINALS.
  • Page 2 NOTES: The maximum distance from the RPM to the PAL-1 is 6 feet. The two modules must be in the same room. Wiring to the printer must be 14 AWG min., 600V insulation in conduit, and located in the same room as the control panel.
  • Page 3 MXL System 1. Installation of the PAL-1 in an MXL system requires that a Siemens model ANN-2 or ANN-3 is installed in the system. The ANN-2 and ANN-3 come installed in an MKB-5 or MKB-6 respectively. An ANN-3 is also included in model RCC-3.
  • Page 4 NOTES: The maximum distance from the FCA2018-U1 to the PAL-1 is 6 feet. The two modules must be in the same room. Wiring to the printer must be 14 AWG min., 600V insulation in conduit, and located in the same room as the control panel.
  • Page 5: Electrical Ratings

    Siemens Building Management System (NCCXP-G or -GL, NCCI7-G or -GL, Desigo CC, and Cerberus DMS) 1. The PAL-1 can be used as a supervised journaling or logging printer when connected to a UL listed Siemens Building Management System computer to meet the requirements of an NFPA 72 proprietary system.
  • Page 6 This page is intentionally blank. Siemens Canada Limited Siemens Industry, Inc. Building Technologies Division Building Technologies Division 2 Kenview Boulevard 8 Fernwood Road Brampton, Ontario L6T 5E4 Canada Florham Park, New Jersey 07932 P/N 315-092408-14 Document ID A6V10372650...