2
Product Information
To ensure safe, economical and environmentally responsible use of the
heating system, we recommend that you read the safety instructions and
operating instructions carefully.
These instructions provide the operator of the heating system with an
overview of the use and operation of the boiler.
2.2
Product data for energy consumption
The following product data satisfy the requirements of the EU Regulations No. 811/2013, No. 812/2013, No. 813/2013 and No. 814/2013
supplementing Directive 2010/30/EU.
Right-hand version
Left-hand version
Product data
Product type
Floor standing condensing
boiler
Nominal heat output
Available heat output
At rated output and high-
1)
temperature operation
At 30 % of rated output and
2)
low-temperature operation
Useful efficiency
At rated output and high-
1)
temperature operation
At 30 % of rated output and
2)
low-temperature operation
Auxiliary power consumption
At full load
At part load
In standby mode
Other data
Standby heat loss
Energy consumption of the
ignition flame
NOx emissions
1) High temperature operation means a return temperature of 60 °C at the boiler inlet, and a flow temperature of 80 °C at the boiler outlet.
2) Low temperature operation means a return temperature (at the boiler inlet) of 30 °C for floor standing condensing boilers, of 37 °C for floor standing boilers,
and 50 °C for other boilers
Table 2 Product data for energy consumption
2.3
Water quality (fill and top-up water)
▶ For information regarding the water quality, see the enclosed
operator's log "Water quality requirements for heat sources made
from aluminium".
Do not use softened water as fill and top-up water.
2.4
Product overview
The Condens 7000 F is a floor standing condensing boiler with an
aluminium heat exchanger.
Condens 7000 F – 6720871579 (2018/07)
8732909990 8732909991 8732909992 8732909993 8732909994 8732909995
8732909996 8732909997 8732909998 8732909999 8732910000 8732910001
Symbol
Unit
–
–
Condens
7000 F-75
–
–
Yes
P
kW
69
rated
P
kW
69.4
4
P
kW
23.1
1
%
88.3
4
%
97.8
1
el
kW
0.083
max
el
kW
0.028
min
P
kW
0.009
SB
P
kW
0.161
stby
P
kW
–
ign
NOx
mg/kWh
41
2.1
Declaration of Conformity
The design and operation of this product conform to European Directives
and the supplementary national requirements. Its conformity is
demonstrated by the CE designation.
You can view the Declaration of Conformity on the internet
( back cover).
Condens
Condens
7000 F-100
7000 F-150
7000 F-200
Yes
Yes
93
140
93.0
139.8
31.0
46.5
88.1
88.1
98.0
97.7
0.156
0.250
0.032
0.046
0.009
0.009
0.161
0.183
–
–
49
34
Product Information
Condens
Condens
7000 F-250
7000 F-300
Yes
Yes
186
233
186.2
233.1
62.1
77.7
88.3
88.2
98.1
98.0
0.234
0.298
0.048
0.049
0.009
0.009
0.247
0.261
–
–
36
32
Condens
Yes
280
280.0
93.0
88.3
97.7
0.336
0.057
0.009
0.298
–
36
5