Wiring

Match your transmitter with the corresponding diagrams
(Figure 4 through Figure 9), set the switches and wire
accordingly. (See Figure 3 below for switch and terminal
block locations.) Ensure that all the installation and wiring is
in compliance with all national and local codes.
Note: All Voltage Outputs are measured with respect to the
POWER SUPPLY / CONTROLLER GROUND.
Wiring for the transmitter should be a shielded, twisted pair,
16-22 AWG. Use only copper conductors. Do not run
transmitter wires and AC power wires together in the same
conduit or wire bundle.
Caution!
Running transmitter wires and AC power wires,
including earth ground, in the same conduit or
wire bundle may cause malfunction due to
electrical noise.
V
I
SW3
V
I
SW1
3K
JPR1
Current
10K
10V
Voltage
J7
J8
5V
Figure 3: Connector/Switch Locations - Inside Cover
V
I
V
I
SW1
SW3
Figure 4: Switch Positions for Voltage Mode
I1XR/P+
Switch Selectable 0-5 Volt or 0-10 Volt Output
I2XR/P–
10V
Voltage
I2-TMP
V-TMP
TH
Thermistor Output*
GND
TH
J8
V-XR
XR 0-5/0-10Vout
5V
I2XR/P–
–GND, 0-5/0-10Vout
I1XR/P+
+V
J7
*To provide a connector for Thermistor
Output, divide the 5-pin terminal block into
XR REPRESENTS
a 3-pin and a 2-pin terminal block as shown.
Dew Point - DP
Enthalpy - EN
Wet Bulb - WB
Figure 5: DP/EN/WB and Temp. (Direct Connection) -
Voltage
Switch Selectable 0-5 Volt or 0-10 Volt Output
10V
Voltage
V-TMP
Temp
GND
GND
V-XR
XR
XR REPRESENTS
5V
I2XR/P–
–V
Dew Point - DP
I1XR/P+
+V
Enthalpy - EN
J7
Wet Bulb - WB
Figure 6: DP/EN/WB and Temp. (Signal Condition) -
Voltage
V
I
V
I
SW3
SW1
Figure 7: Switch Positions for Current Mode
Current*
V in
I1XR/P+
XR (4-20mA) out
I2XR/P–
I2-TMP
TH
Thermistor Output
TH
J8
XR REPRESENTS
*Shipped in 4-20mA output.
Dew Point - DP
Enthalpy - EN
Wet Bulb - WB
Figure 8: DP/EN/WB and Temp. (Direct Connection) -
Current
Current*
V in
I1XR/P+
XR RTN
I2XR/P–
Temp RTN
I2-TMP
TH
XR REPRESENTS
TH
J8
Dew Point - DP
Enthalpy - EN
*Shipped in 4-20mA output.
Wet Bulb - WB
Figure 9: DP/EN/WB and Temp. (Signal Condition) -
Current
HumiTrac™ XR Transmitter Series
Installation Guide
Wiring (cont.)
CE COMPLIANCE
Ensure that the probe earth ground wire (for Duct and
1.
Outside Air units only), the shield wire and the PCB earth
ground wire are connected to the mounting screw or the
NEAREST (<1.5m) earth ground.
The other end of the shield wire MUST be connected to
2.
the power supply /controller earth ground ONLY.
Hold the sides of
the sensor tip
near the base of
the sintered filter.
Caution: Remove power before replacing the sensor.
Figure 10: Remove/Install the Sensor Tip
Table 1: HumiTrac XR Ordering Information
Model
Product Information
Space
HUMI-DP-XR-S
DEW POINT TRANSMITTER-SPACE MOUNT
(Wall)
HUMI-EN-XR-S
ENTHALPY TRANSMITTER-SPACE MOUNT
Mount
HUMI-WB-XR-S
WET BULB TRANSMITTER-SPACE MOUNT
Duct Mount
HUMI-DP-XR-D
DEW POINT TRANSMITTER-DUCT MOUNT
HUMI-EN-XR-D
ENTHALPY TRANSMITTER-DUCT MOUNT
HUMI-WB-XR-D
WET BULB TRANSMITTER-DUCT MOUNT
Air Mount
HUMI-DP-XR-O
DEW POINT TRANSMITTER-OPEN AIR
HUMI-EN-XR-O
ENTHALPY TRANSMITTER-OPEN AIR
HUMI-WB-XR-O
WET BULB TRANSMITTER-OPEN AIR
A40254250
,Rev. A (August 2009)