11. PIPING DESIGN
Note: 1
To connect multiple indoor units to a port
Maximum total capacity of connected indoor units: W(P)80 or below
Maximum number of connectable indoor units: 3 units
Branch joints are field-supplied.
All the indoor units that are connected to the same port must be in the same group and Thermo-ON/OFF operation
simultaneously. For all the indoor units in the group, the room temperature needs to be monitored via the connected
remote controller.
When connecting a W(P)71 through 125 model of indoor unit to an HBC controller, the pipes connecting the unit to
the same set of HBC controller ports cannot be branched out to connect additional units.
When connecting multiple indoor units including a W(P)63 unit to the same set of HBC ports, use a size 32A pipe
in the section indicated as "b' and c" and connect the W(P)63 unit to the pipe indicated as "c" in the figure.
(See page 74.)
Note: 2
Connecting W(P)100 or 125 indoor units to an HBC controller
When connecting W(P)100 or 125 indoor units to an HBC controller, connect each unit to two sets of two ports on
the HBC controller, using two Junction pipes (Y-joints). (See Fig. 11-2-1A.)
Connect an increaser (20A-to-32A) to the merged side of each junction pipe. (See Fig. 11-2-1A.)
When connecting junction pipes to HBC ports, the branched sides of the junction pipes cannot be connected to
combinations of ports "4 and 5," "8 and 9," or "12 and 13." (See Fig. 11-2-1B.)
When connecting a W(P)100 or a 125 model of indoor unit to an HBC controller, the pipes connecting the unit to the
same set of HBC controller ports cannot be branched out to connect additional units.
Note: 3
Maximum connectable capacity of indoor units to HBC
HBC has two pumps. Each pump can accommodate the capacity of indoor units equivalent to W(P)175.
Make sure that the total capacity of the indoor units connected to "ports 1 through 4 and 9 through 12" or "5 through
8 and 13 through 16" will not exceed W(P)175. (See Fig. 11-2-1B.)
MEES18K068
R2-Series
77