Output Relays; Output Relay Function Assignment - GE P50 Agile P253 Technical Manual

Motor protection relay
Table of Contents

Advertisement

8 Monitoring & Control
interface, the Opto I/P can be assigned to any function from I/O configuration menu. The function can
be assigned to any input by entering the values to them either 0 or 1 i.e. 0 = not assigned and 1 =
assigned.
The following are the list of functions, which can be assigning to digital input.
Function
Rem. Rst.
CBF Init.
Sel Grp2
Ext Trip
DR Trig
CB (52A)
CB (52B)
Blk I>1
Blk I>2
Blk I>3
Blk I2>1
Blk I2>2
Blk I2>3
Blk IN1>1
Blk IN1>2
Blk IN1>3
Blk IN2>1
Blk IN2>2
Blk IN2>3
Blk THOL
Blk I<
EmerRest
Speed Sw
TCS Trig
The digital inputs are suitable for accepting AC or DC auxiliary supply. The selection for AC or DC
auxiliary supply is done from submenu Opto I/P under SYSTEM DATA menu.
The DI can be selectable for different operating voltage (ordering option) depending on the application
requirement.
For details regarding the operating voltage and its threshold values, please refer to the Technical
Specification section of this manual.
2.6

Output Relays

The device supports 6 numbers of relay output. The use of these relay outputs depends on the
application. There are a number of settings associated with the relay outputs.
2.6.1

Output Relay Function Assignment

The relays have configurable logic outputs, which can be assigned to any available function. The logic
outputs are identified as RL1 to RL6. All logic outputs have changeover contacts and can be
configured to change state on activation of the different functions available in the relay. A basic output
matrix is included in the P50 Agile configurator. Different functions can be assigned by using P50
Configurator as well as relay user interface. On the user interface the output relays can be assigned
8-8
Function used to reset Latch type output contact and LED indication
Function used to Initiate Breaker Fail
Function used to enable Group 2 setting
Function initiates the relay assigned for Gen. Trip to operate and trip the CB.
Function used to trigger Disturbance Record
Status used to detect CB Close position
Status used to detect CB Open position
Function used to block tripping of O/C stage 1
Function used to block tripping of O/C stage 2
Function used to block tripping of O/C stage 3
Function used to block tripping of NPS stage 1
Function used to block tripping of NPS stage 2
Function used to block tripping of NPS stage 3
Function used to block tripping of measured E/F stage 1
Function used to block tripping of measured E/F stage 2
Function used to block tripping of measured E/F stage 3
Function used to block tripping of derived E/F stage 1
Function used to block tripping of derived E/F stage 2
Function used to block tripping of derived E/F stage 3
Function used to block tripping of Thermal Overload
Function used to block tripping of Under Current
Function used to restart motor in emergency condition.
Function used for detection of locked rotor condition
Status is used to monitor Trip Circuit Supervision
Description
P50 Agile P253
P253/EN M/C