6
C E M 1 1 - F B P. X X X E A R T H L E A K A G E M O N I T O R M A N U A L
—
CEM11-FBP.60
Rotary switch set to
0
1
2
3
4
5
6
7
8
9
—
CEM11-FBP.120
Rotary switch set to
0
1
2
3
4
5
6
7
8
9
Earth fault current threshold [mA]
120
1000
2000
2800
4000
4800
6000
6800
for functional test
for functional test
Earth fault current threshold [mA]
240
2000
4000
5600
8000
9600
12000
13600
for functional test
for functional test
Comment
Tolerance ± 30 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Comment
Tolerance ± 30 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %
Tolerance ± 10 %