Downloading Projects - Siemens DTU3005-B Operator's Manual

Intelligent data transfer device for connection to plcs and modbus networks
Table of Contents

Advertisement

7
Transferring Project Files
.
Figure 7.1 Null Modem Cable connection
The null modem cable will cross pins 2 and 3 (RXD
and TXD). On the computer end of the cable, pins 7
and 8 (RTS and CTS) should be connected together.
Also pins 1, 4, and 6 (DCD, DTR and DSR) should be
connected together. The cable diagram is illustrated in
Figure 7.1. In addition, the DIP switches on the front of
the DTU3005B unit must be set to configuration mode
as described below.
1.
Power down the DTU3005B unit.
2.
Set the DIP switches to configuration mode per
the DIP switch settings listed below in Table 7.1
and shown in Figure 7.1.
3.
Restart the DTU3005B unit.
4.
The status LED on the front of the DTU3005 unit
flashes green to indicate that the unit is in config-
uration mode.
Note: To return the device to normal opera-
tion, the DTU3005B unit must be pow-
ered off while the DIP switch settings
are reset, then the unit will be in normal
operation mode when it is powered up.
Table 7.1 Mode Switch Settings
Mode
Switch 1
Switch 2
Normal
Off
Off
Operation
Configura-
Off
Off
tion
50
Figure 7.2 DIP Switch Settings for Normal Operation
and Configuration Modes (Switch 4 is N/A)
7.1
Select Download project to DTU3005 from the Trans-
fer menu, and the following screen appears.
Select Ok and the DTU3005 Editor software transfers
the currently displayed project to the DTU3005 unit.
Switch 3
Status
LED
Off
On
steady
On
Flashing
Green

Downloading Projects

Siemens Energy & Automation, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents