6 Commissioning
6.4.8

Motor potentiometer (MOP)

Setpoint memory of the MOP
P1031 =...
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or
power down.
0
MOP setpoint will not be stored
1
MOP setpoint will be stored (P1040 is updated)
Inhibit negative MOP setpoints
P1032 =...
0
Neg. MOP setpoint is allowed
1
Neg. MOP setpoint inhibited
P1040 =...
Setpoint of the MOP
Determines setpoint for motor potentiometer control.
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.
Possible parameter settings for the selection of MOP:
DIN
BOP
USS on
BOP link
USS on
COM link
CB
40
Selection
P0719 = 0, P0700 = 2, P1000 = 1
or
P0719 = 1, P0700 = 2
P0719 = 0, P0700 = 1, P1000 = 1
or
P0719 = 11
P0719 = 0, P0700 = 4, P1000 = 1
or
P0719 = 41
P0719 = 0, P0700 = 5, P1000 = 1
or
P0719 = 51
P0719 = 0, P0700 = 6, P1000 = 1
or
P0719 = 61
MOP up
MOP down
P0702 = 13
P0703 = 14
(DIN2)
(DIN3)
UP button
DOWN button
USS control word
USS control word
r2032 Bit13
r2032 Bit14
USS control word
USS control word
r2036 Bit13
r2036 Bit14
CB control word
CB control word
r2090 Bit13
r2090 Bit14
MICROMASTER 440
Operating Instructions (Compact)
Issue 10/06
0
1
5.00 Hz