Download Print this page

Installation - Toshiba CV-10HA Instruction Manual

High-voltage vacuum contractors, motor & transformer application, 12/15kv-320a-5/4ka
Hide thumbs Also See for CV-10HA:

Advertisement

TOSHIBA

5. INSTALLATION

When installing , protect from dust. Particularly when the contactor
is installed while the building is under construction , shield it from
cement dust and other foreign matter.
The following prec:autions should be taken.
(1) The mounting surface must be horizontal (level : less than +l mm).
When the mounting surface is not horizontal , adjust with spacers.
(2) There are four mounting holes.
Use Ml 0 bolts to securely mount the contactor.
(3) In wiring the main circuit terminals, ground terminals and control
circuit , wires should be given sufficient length to be flexible.
The ground wires should be more than 5.5mm in cross section.
(4) Do not mount the contactor with its front inclined downward.
This may result in malfunction.
(5) Do not touch the vacuum interrupter surface with soiled hands.
(6) When it is applied to a capacitor load , be sure to used a space heater
to keep humidity low.
CAUTION : Do not install on energize contactor that has been bad condition.

Advertisement

loading

This manual is also suitable for:

Cv-10hal