Table 31. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 32. Operating temperature derating specification
Operating temperature
derating
Up to 35°C (95°F)
35°C to 40°C (95°F to
104°F)
40°C to 45°C (104°F to
113°F)

Standard operating temperature

Table 33. Standard operating temperature specifications
Standard operating temperature
Continuous operation
(For altitude less than 950 m or 3117 ft)

Expanded operating temperature

Table 34. Expanded operating temperature specifications
Expanded operating
temperature
Continuous operation
≤ 1% of annual operating
hours
NOTE: When operating in the expanded temperature range, the performance of the system may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.
Expanded operating range
The operating temperature is specified for a maximum altitude of 950 m for expanded operating range.
Do not perform cold start at 5°C or lower, due to hard drive constraints.
40
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature reduces by 1°C/300 m (1°F/547 ft), above 950 m (3,117 ft).
Maximum temperature reduces by 1°C/175 m (1°F/319 ft), above 950 m (3,117 ft).
Maximum temperature reduces by 1°C/125 m (1°F/228 ft), above 950 m (3,117 ft).
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate
continuously in temperatures as low as 5°C and as high as 40°C.
For temperatures 35°C to 40°C, derate maximum allowable temperature by 1°C per 175 m (1°F per
319 ft) above 950 m (3,1171 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C–35°C), the system can operate
down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, derate maximum allowable temperature by 1°C per 125 m
(1°F per 228 ft) above 950 m (3.117 ft).
Specifications
10°C to 35°C (50°F to 95°F)
with no direct sunlight on the equipment.