Tightening torques for screw connections
The following tightening torques apply when tightening current-conducting connections (DC
link connections, motor connections, busbars, cable lugs) and other connections (ground
connections, protective ground connections, steel threaded connections/glands).
Table 4- 3
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC
Tightening torques for screw connections
Thread
Ground connections, protective
ground connections, steel threaded
M6
M8
M10
M12
connections/glands
10 Nm
25 Nm
50 Nm
88 Nm
Electrical installation
Aluminum threaded connec-
tions/glands, plastic, busbars,
cable lugs
6 Nm
13 Nm
25 Nm
50 Nm
25