Advertisement

5.2. Transferring the configuration to an inverter

This procedure allows the user to select the configuration file to be transferred to the inverter.
The user must already have:
-Loaded the inverter configuration file ("*.CFG") onto the Parameter writer (see section
OR
-Generated the configuration file using PCM software and loaded this file onto the Parameter writer
STEP
• Turn the Parameter writer on using the ON/OFF button "F" (see section 3.2).
• Connect the Parameter writer to the inverter using the RJ45 cable (see section 4.2).
1
• Press "ENT" when the screen displays "Main menu / Action".
• Press "ENT" when the screen displays "Action Config / MLD -> Device".
• Select the file to be transferred using the arrow keys and press "ENT" to start the transfer.
2
(see section 6.7).
• The configuration has been transferred successfully from the Parameter writer. Disconnect
3
the RJ45 cable from the inverter.
• Pressing "ENT" returns the user to the "Action Config / MLD -> Device" menu.
Note :
• Keep on pushing ESC key if the process of searching communication mode is canceled.
• Display is changed faster by keeping on pushing
Main menu
1
Action
ENT
Action Config
MLD -> Device
ENT
Action Config
XXXXXXXX
MLD -> Device
MLD -> Device
Filename1
Filename2
ENT
FilenameX
>>>>
FilenameX
>>>>>>>>
FilenameX
>>>>>>>>>>>>
Store config
Successful
ENT
2
MLD -> Device
FilenameN
ENT
ENT
3
Procedure
or
key.
14
E6581680