Beko METPOINT PRM SP11 Instructions For Installation And Operation Manual

Pressure transducer

Advertisement

Quick Links

EN - English
Instructions for installation and operation
®
Pressure transducer METPOINT
PRM
SP11

Advertisement

Table of Contents
loading

Summary of Contents for Beko METPOINT PRM SP11

  • Page 1 EN - English Instructions for installation and operation ® Pressure transducer METPOINT SP11...
  • Page 2 Dear customer, ® Thank you for deciding in favour of the METPOINT PRM SP11 pressure transducer. Please read these installation and operating instructions carefully before mounting and starting up the pressure transducer and follow our directions. Perfect functioning of the pressure transducer can only be guaranteed when the provisions and notes stipu- lated here are strictly adhered to.
  • Page 3: Table Of Contents

    Inhalt Contents Pictograms and symbols ........................4 Signal words in accordance with ISO 3864 and ANSI Z 535 ..............4 General information ..........................5 Safety instructions ..........................6 Proper use .............................. 7 Exclusion from the field of application ....................7 Type plate ...............................
  • Page 4: Pictograms And Symbols

    Signal words in accordance with ISO 3864 and ANSI Z 535 Pos : 25 /Beko T ec hnis che D okumentati on/Sic her hei t/Sig nal worte ISO + AN SI @ 0\mod_1213340310421_6.doc x @ 8739 @ @ 1 Danger!
  • Page 5: General Information

    PRM. The operating instructions must be accessible at all times at the place of application of the device. If you have any queries regarding these instructions, please contact BEKO TECHNOLOGIES GMBH. Installation works must exclusively be carried out by authorised and qualified personnel. Prior to undertaking any measures, the qualified personnel shall read up on the device by carefully studying the operating instructions.
  • Page 6: Safety Instructions

    Safety instructions Safety instructions Danger! Compressed air! Risk of serious injury or death through contact with quickly or suddenly escaping compressed air or through bursting plant components. Measures • Do not exceed the max. operating pressure (see type plate)! • Only use pressure-resistant installation material! •...
  • Page 7: Proper Use

    Proper use Proper use ® The METPOINT PRM pressure transducer detects the relative pressure (gauge pressure) in gaseous and liquid media and transforms this measured value into a linear output signal 4 … 20 mA or 0 … 10 V. Pressure transducers transform the physical pressure into a pressure-proportional electrical signal.
  • Page 8: Type Plate

    Type plate Type plate ® The type plate is on the housing. It includes all the important data regarding the METPOINT PRM pressure transducer which must be communicated to the manufacturer or supplier upon request. ® METPOINT Product designation S/N: Serial number P/N: Item number...
  • Page 9: Technical Data

    Technical data Technical data General indications PRM SP11 Model designation Measuring principle Stainless-steel thin film technology Measured parameter Overpressure (gauge pressure) Output signal, type PRM SP21 4 ... 20 mA, analogue, 2-wire 0 … 16 bar Measuring range Overload pressure limit 32 bar Burst pressure 125 bar...
  • Page 10 Technical data Materials Sensor element (in contact with the medi- 1.4548 Process connection (in contact with the 1.4404, EN 10272, EN 10088-3 medium) Housing 1.4404, EN 10272, EN 10088-3 Mounting connector CuZn, Au, PA, FKM / EPDM Permissible temperature ranges Process-medium temperature -40 …...
  • Page 11 Technical data Mechanical stresses Vibration resistance/vibrations according to EN 60068-2-6 25 … 2000 Hz, 20 g, sine Mechanical shock resistance according to EN 60068-2-27 50 g, 11 ms, half-sine CE conformity Pressure Equipment Directive 97/23/EC EMC Directive 2004/108/EC EMC immunity to interference, industrial field EN 61326-1 &...
  • Page 12: Dimension Drawings

    Dimension drawings Dimension drawings Dimensions PRM SP11 ® METPOINT SP11...
  • Page 13 Dimension drawings Dimensions and connections PRM SP11 Connection adapter, R¼ and ¼-NPT, width A/F (German "Schlüsselweite") 27 Standards for threads Straight pipe thread (internal and external screw thread) for a non-sealing connection in the thread Short symbol G, according to ISO 228-1 Tapered external pipe thread for a sealing connection in the thread Short symbol R, according to EN 10026-1 Tapered external pipe thread for a sealing connection in the thread...
  • Page 14: Function

    Function 10 Function ® The METPOINT pressure transducer of the PRM-SP series de- tects the relative pressure (gauge pressure) in gaseous and liq- uid media and transforms this measured value into a linear, pres- sure-proportional electrical output signal of 4 … 20 mA or 0 … 10 ®...
  • Page 15: Installation

    Installation 11 Installation 11.1 Installation instructions Warning! Risk of injury in the event of insufficient qualifications! Improper lead significant personal injury material damage. All of the activities described in these operating instructions must only be carried out by qualified personnel with the qualifications described hereinafter. Qualified personnel Due to the specific training and knowledge concerning the measuring and control technology, and due to their experience and knowledge of the country-specific provisions, standards in force and directives, qualified...
  • Page 16: Preparing The Thread At The Measurement Point

    Installation 11.2 Preparing the thread at the measurement point In order to install the pressure transducer, a receiving thread is required at the measuring point. The latter must already show the following specifications or must be prepared correspondingly: 11.3 Installation example for connections in accordance with EN 837-1 with a cylindrical thread In order to seal the process connection (1) with a cylindrical thread (3) at the sealing surface (4), flat gaskets (2) are employed.
  • Page 17: Electrical Installation

    Electrical installation 12 Electrical installation The nominal value for the supply voltage for the electrical installation is 24 V DC. ® Supply of the METPOINT PRM SP11 must be implemented with a stabilised, short-circuit-protected power supply that is protected against overvoltage. The energy supply must come from a source with an energy- limited electrical circuit (10 A max./ 30 V max.) and a protective separation from the network.
  • Page 18: Pin Assignment Prm Sp11, 2-Wire

    Electrical installation 12.1 Pin assignment PRM SP11, 2-wire Function Description Conductor colouring PIN-1 Positive (+) connection of the supply voltage Brown PIN-2 Not used PIN-3 Current output Blue PIN-4 Not used Connection diagram PRM 11, 2-wire system, current output 4 … 20 mA Notes: ®...
  • Page 19 Electrical installation The following advice applies to the connection: Shielding is implemented via the shield ring of the connector. The preconditions for proper shielding are that the respective connector is made of metal and that the shield has the shape of a braid. The shielding must be earthed at one end.
  • Page 20: Maintenance And Calibration

    Maintenance and calibration 13 Maintenance and calibration The perfect and safe functioning of the components requires calibration or adjustment at regular intervals. ® The METPOINT PRM SP11 should be calibrated annually and re-adjusted, if required. Danger! Compressed air! Risk of serious injury or death through contact with quickly or suddenly escaping compressed air or through bursting and/or unsecured plant components.
  • Page 21: Cleaning/Decontamination

    Maintenance and calibration 13.1 Cleaning/decontamination ® Cleaning of the METPOINT PRM SP11 must be undertaken using a slightly damp (not wet) cotton cloth or one-way wipe, and mild, commercially available cleaner/soap. For decontamination, spray the cleaner on an unused cotton cloth or one-way wipe and wipe the component comprehensively.
  • Page 22: Scope Of Delivery

    Scope of delivery 14 Scope of delivery Illustration Description ® 1 x pressure transducer METPOINT PRM SP11 (0 … 16 bar) 4 … 20 mA 1x M12 plug, straight 1 x copper seal Wiithout illustration 1 x test record ® METPOINT SP11...
  • Page 23: Accessories

    Accessories 15 Accessories Description Order no. M12 connector, angle (incl. 5 m cable, pre-assembled) 4025252 Connection adapter R ¼“, SW27 4025381 Connection adapter NPT ¼“, SW27 4025382 Copper seal 4025383 Connecting cable 4 x 0.34 mm² (AWG 22) Upon request ®...
  • Page 24: Dismantling And Diposal

    Dismantling and disposal 16 Dismantling and disposal When dismantling the PRM SP11 pressure transducer, all related parts and operating media must be dis- posed of separately. Waste code: 20 01 36 Used electrical and electronic devices with the exception of those which come under 20 01 21, 20 01 23, and 20 01 35.
  • Page 25: Trouble Shooting And Fault Removal

    Trouble shooting and fault removal 17 Trouble shooting and fault removal Symptoms Possible reasons Measures There is no signal. Break of the signal line Check the passage Output signal = 0 mA There is no signal. Check the wiring. Incorrect wiring of the plug Observe the PIN assignment.
  • Page 26: Declaration Of Conformity

    Declaration of conformity 18 Declaration of conformity BEKO TECHNOLOGIES GMBH 41468 Neuss, GERMANY Tel: +49 2131 988-0 www.beko-technologies.com EC Declaration of Conformity We hereby declare that the products indicated hereafter comply with the stipulations of the relevant direc- tives and technical standards. This declaration only refers to products in the condition in which they have been placed into circulation.
  • Page 27: Index

    Index 19 Index Accessories 23 Fault removal 25 ANSI Z 535 4 Field of application 7 Check 20 Function 14 Components 22 Installation and operating instructions 4 Connection adapter, R ¼ and ¼ NPT 13 ISO 3864 4 Danger compressed air 5, 15, 17, 20, 21, 24, 25 Maintenance 20 Data 9 Maintenance works 15, 21...
  • Page 28 Tel.: +81 44 328 76 01 info@beko-technologies.co.jp Benelux Polska / Poland Scandinavia BEKO TECHNOLOGIES B.V. BEKO TECHNOLOGIES Sp. z o.o. www.beko-technologies.com ul. Chłapowskiego 47 Veenen 12 NL - 4703 RB Roosendaal PL-02-787 Warszawa Tel.: +31 165 320 300 Tel.: +48 (0)22 855 30 95 info@beko.nl...