Wiring Setups For Hazardous Area Installations - Siemens SITRANS Probe LU Quick Start Manual

Hart
Hide thumbs Also See for SITRANS Probe LU:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
1.
Strip the cable jacket for approximately 70 mm
(2.75") from the end of the cable, and thread the
wires through the gland
2.
Connect the wires to the terminals as shown
above: the polarity is identified on the terminal
block.
3.
Tighten the gland to form a good seal.
4.
Close the cover and tighten screws: please do
not overtighten screws. Recommended torque is
1.1 to 1.7 N-m (10 to 15 in-lb).
.
1

Wiring setups for hazardous area installations

Always check the device nameplate and process device tag to verify the approval rating.
1. Intrinsically Safe wiring
Device nameplate (ATEX/IECEX/INMETRO/C-TICK)
SITRANS Probe LU
7MLxxxx-xxxxx-xxxx
Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Serial No: GYZ / B1034567
Power Rating: 24V
Nom., 30V
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
The ATEX certificate can be downloaded from the product
page of our website at: www.siemens.com/probelu. Go to Support > Approvals /
Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 13.0008X.
Device nameplate (FM/CSA)
SITRANS Probe LU
7ML1234-78910-ABC-D
Amb.Temp.: – 40°C to 80°C
Serial No: GYZ / S1034567
Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Power Rating: 24V
Nom., 30V
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
FM Intrinsically Safe connection drawing number 23650516, and CSA Intrinsically Safe
connection drawing number 23650517 can be downloaded from the product page of our
website at: www.siemens.com/probelu. Go to Support > Installation Drawings > Level
Measurement > Continuous - Ultrasonic.
For power demands see
For wiring requirements: follow local regulations.
Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67
Instructions specific to hazardous area installations (Reference European
Refer to
ATEXDirective 94/9/EC, Annex II, 1/0/6)
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
Page EN-6
SITRANS Probe LU (HART) – QUICK START MANUAL
1
.
Max., 4-20 mA
HART
Max., 4-20 mA
Loop Voltage versus Loop Resistance
,
terminals for
loop current
U i = 30 V
I i = 120 mA
P i = 0.8 W
C i = 3.6 nF
L i = 0 mH
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA - VEJA INSTRUÇÕES
Class I, Div 1, Group A, B, C, D
Class II, Div 1, Group E, F, G
Class III
Temp. Code: T4
CSA per drawing: 23650517
FM per drawing: 23650516
WARNING: Possible static hazard, do not rub or clean on site.
IP68 locations.
on page 7.
cable
KCC-REM-S49
PROBELU
Ex ia IIC T4 Ga
DNV 12.0070 X
II
1 G
0518
Ex ia IIC T4 Ga
SIRA 06ATEX2355X
IECEx SIR 13.0008X
Vmax = 30 V
HART
Imax = 120 mA
Pmax = 0.8 W
Ci = 3.6 nF
Li = 0.5 mH
159134
on page 4.
A5E32168031