Troubleshooting; Programmable Controller Troubleshooting - Mitsubishi Electric MELSEC Q Series Quick Start Manual

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Troubleshooting

When modules do not run normally, refer to the following troubleshooting information.
 Programmable controller troubleshooting
1.
First, check the following points.
1) The ON/OFF status of the power supply
2) The mounting condition of the power supply module, the CPU module, and the I/O modules
3) The LED on the front of the CPU module
2.
Check the problem and respond according to the following list.
Problem
The "POWER" LED is
OFF after turning ON the
power supply module.
The "ERR." LED on the
CPU module is flashing
red.
The "BAT" LED on the
CPU module is ON or
flashing.
Reference
For details of the troubleshooting, refer to the following manual.
QCPU User's Manual (Hardware Design, Maintenance and Inspection):
SH-080483ENG
28
Check
Is the power supply module
properly wired and
mounted?
Are programs and PLC
parameters written to the
CPU module?
If the CPU has several
programs, are they
registered to the PLC
parameter?
Other than above
Is the battery properly
connected?
Action
Wire and mount the module properly.
3 Mounting Modules (P.10)
4 Wiring Modules (P.11)
Write programs and parameters to the CPU
module.
7 Writing Programs (P.21)
If there are several programs, register them in the
program setting of the PLC parameter, and write
the parameters to the CPU module.
If several programs are not needed, delete
unnecessary data, or execute the Format PLC
memory function before writing data to the
programmable controller CPU.
GX Developer Version 8
Operating Manual: SH-080373E
Handle by checking for errors following "Checking
errors in the CPU module" (P.30) in this manual.
Properly connect the battery.
3 Mounting Modules (P.10)