Mechanical installation

3.2 Installing the braking resistor

3.2
Installing the braking resistor
The braking resistor should not be installed in the vicinity of the converter. The following
points must be taken into account:
● The braking resistors are only suitable for floor mounting.
● The maximum cable length between the Braking Module and braking resistor is 100 m.
● Sufficient space must be available for dissipating the energy converted by the braking
resistor.
● A sufficient distance from flammable objects must be maintained.
● The braking resistor must be installed as a free-standing unit.
● Objects must not be placed on or anywhere above the braking resistor.
● The braking resistor should not be installed underneath fire detection systems, since
these could be triggered by the resulting heat.
● For outdoor installation, a hood must be provided to protect the braking resistor from
precipitation (in accordance with degree of protection IP20).
Figure 3-1
Dimension drawing for braking resistor (50 kW)
14
Operating Instructions, 10/2016, A5E32845373B AD