HP MCS G2 Installation Overview

Modular cooling system
Hide thumbs Also See for MCS G2:

Advertisement

Quick Links

HP Modular Cooling System G2
Installation Overview

Advertisement

Table of Contents
loading

Summary of Contents for HP MCS G2

  • Page 1 HP Modular Cooling System G2 Installation Overview...
  • Page 2: Safety Information

    MCS G2 kit contents HP MCS G2 unit installed on an HP 10000 G2 Series Rack (1) • Automatic Door Release kit (1) •...
  • Page 3 MCS unit and the rack until you the unit can cause significant damage. can remove the rear caster plate. Route the water hoses from the HP Hook-Up Kit through the floor cut-out. Remove the rear caster plate.
  • Page 4 11. Cap the unused side of each T-fitting on the MCS unit using the 14. Plug the network cable into the RJ-45 connector on the power cap wrench. inlet box. 12. Route the two drain hoses to the drain collection system catch 15.
  • Page 5: Powering Up And Configuring The Unit

    21. (Optional) Secure the access panel to the brackets on the MCS Flow control: none frame using two M6 flathead screws. Log in to the HP Modular Cooling System Configuration Utility. a. In the login field, enter the user name. The default user name is Admin.
  • Page 6 To return to the Main Menu screen, press Esc. Enter 3 IP Def. Router, and then enter the gateway. Access the HP Modular Cooling System Configuration Utility. Activate the values. a. Return to the Main Menu Network Configuration screen.
  • Page 7 13. Click Setup>Accounts, and then change the default Web b. Enter 4 Activate Actual Values. Admin and Web User passwords. c. To reboot, enter y at the prompt. You must reboot to activate the IP settings, product ID, and serial number values.
  • Page 8: Configuring The Ip Address Through The Web Interface

    Log in to the new IP address. 21. Click Save Settings. For more information on adjusting the management module settings through the web interface, see the HP Modular Cooling System G2 Web Interface User Guide located on the Documentation CD shipped with this product.
  • Page 9 Setup>Management>SNMP Managers. 14. Click Save Settings. For more information on adjusting the management module settings through the web interface, see the HP Modular Cooling System G2 Web Interface User Guide located on the Documentation CD included with this product.
  • Page 10: Legal Notices

    © Copyright 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty.

Table of Contents