3. United Kingdom
CIBSE
Application
Factories
Offices (open plan)
Shops, department stores, and supermarkets
Theaters
Dance halls
Hotel bedrooms
Laboratories
Offices (private)
Residences (average)
Restaurant (cafeteria)
Cocktail bars
Conference rooms (average)
Residence
Restaurant
Board rooms, executive offices, and
conference rooms
Corridors
Kitchens (domestic)
Kitchens (restaurant)
Toilets
•
CHAPTER 10
Ventilation Standards in Each Country
Outdoor air
Recommended
Per person
8 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
18 l/s /person
12 l/s /person
18 l/s /person
12 l/s /person
18 l/s /person
12 l/s /person
18 l/s /person
12 l/s /person
25 l/s /person
18 l/s /person
N/A
N/A
N/A
N/A
Minimum
Per person
Per m
5 l/s /person
0.8 l/s / m
5 l/s /person
1.3 l/s / m
5 l/s /person
3.0 l/s / m
5 l/s /person
8 l/s /person
8 l/s /person
1.7 l/s / m
8 l/s /person
8 l/s /person
1.3 l/s / m
8 l/s /person
8 l/s /person
6.0 l/s / m
N/A
1.3 l/s / m
N/A
10.0 l/s / m
N/A
20.0 l/s / m
N/A
10.0 l/s / m
Smoking
2
2
None
2
Some
2
Some
—
Some
—
Some
2
Heavy
—
Some
2
Heavy
—
Heavy
—
Heavy
—
Heavy
—
Some
—
Heavy
—
Heavy
Very
2
Heavy
2
N/A
2
N/A
2
N/A
2
N/A
U-89