SITRANS LR 200 and SIMATIC PDM
Connecting SITRANS LR 200 to SIMATIC PDM using HART
Objective:
Equipment:
While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied.
Overview:
SIMATIC PDM is the Siemens configuration software used to set up the SITRANS LR 200. All parameters are accessed through
PDM and projects containing configuration data are saved. SIMATIC PDM also provides diagnostic information, permitting the
user to view echo profiles and check set points.
To ensure that SIMATIC PDM connects properly, please complete the two processes outlined in Initial Setup:
Updating the Device Description
De-activating Buffers
This Application Guide discusses the following
setting up SIMATIC PDM
setting up a HART network
adding the SITRANS LR 200 HART to a project
viewing and editing parameters
using SIMATIC PDM LifeList for quick access
HART is a registered trademark of the HART Communication Foundation.
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225, Peterborough, ON Canada K9J 7B1
Tel: (705) 745-2431 Fax: (705) 741-0466
Email: techpubs@siemens-milltronics.com
Become familiar with the SITRANS LR 200 wiring requirements and HART modem
Become familiar with SIMATIC PDM configuration tool
SITRANS LR 200 instrument
SITRANS LR 200 instruction manual
SIMATIC PDM ver. 5.2 (SP. 1)
www.siemens-milltronics.com
APPLICATION GUIDE
modem
HART modem interface
Terminal screwdriver
PC or Laptop
AG030616

Advertisement

loading

Summary of Contents for Siemens SITRANS LR 200

  • Page 1 While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied. Overview: SIMATIC PDM is the Siemens configuration software used to set up the SITRANS LR 200. All parameters are accessed through PDM and projects containing configuration data are saved. SIMATIC PDM also provides diagnostic information, permitting the user to view echo profiles and check set points.
  • Page 2 The latest SITRANS LR 200 HART device description for Simatic PDM is available for free download on www.siemens- milltronics.com: Go to Downloads on the SITRANS LR 200 product page and select HART Device Descriptor version 1.95 for SIMATIC PDM. Save the ZIP file to a directory on your terminal and then double click to open it.
  • Page 3 Using the instruction manual as a guide, terminate the wires inside the LR 200 housing to the appropriate terminals. Connect the HART modem across the wires powering the SITRANS LR 200. These wires must be terminated across a 250 Ohm resistor in series with the loop.
  • Page 4 Right click HART modem in Process Device Network View window and select Insert New Object/HART device to open the Insert Device Objects window. Fill in Name field and leave the Address at 0 SITRANS LR 200 and SIMATIC PDM AG030616 4 of 8...
  • Page 5 Click OK to re-open Process Device Network View window. Double click LR 200 to open the User ID window. Select Specialist and click OK. Go to Sensors/Level/ Echo/SIEMENS MILLTRONICS and double click Sitrans LR 200 to open the device window. SITRANS LR 200 and SIMATIC PDM...
  • Page 6 SIMATIC PDM provides full access to the SITRANS LR 200 parameters and to PDM’s features. The parameters used to operate the SITRANS LR 200 are accessed through the folder tree in the left pane of the LR 200 Project Manager window. The PDM application review features are accessed through the Project Manager Window menu bar.
  • Page 7 PDM LifeList gives you immediate access to the instruments connected to your terminal. Settings can be monitored and parameters can be changed; however, these changes will not be reflected in the SITRANS LR 200 permanent project file. They can be saved upon exit and may then be used to change settings after PDM is accessed in the standard fashion.
  • Page 8 10. Click File and then Exit to close the LifeList window. You have the option of saving the data as a PDM file and import it into a project file. NOTE For information on loading information into PDM, please consult PDM Help SITRANS LR 200 and SIMATIC PDM AG030616 8 of 8...