4-3. Objects
Support status for objects and for BACnet
Object type
*1
Access Credential
Access Door
Access Point
Access Rights
Access User
Access Zone
Accumulator
Analog Input
Analog Output
Analog Value
Averaging
Binary Input
Binary Output
Binary Value
BitString Value
Calendar
CharacterString
Value
Command
Credential Data Input (37)
Date Pattern Value
Date Value
DateTime Pattern
Value
DateTime Value
Device
Event Enrollment
Event Log
WT07919X04
®
functions are listed below.
Supported/
Abbreviation
Not supported
(32)
—
(30)
—
(33)
—
(34)
—
(35)
—
(36)
—
(23)
AC
(0)
AI
(1)
—
(2)
AV
(18)
—
(3)
BI
(4)
BO
(5)
BV
(39)
—
(6)
—
(40)
—
(7)
—
—
(41)
—
(42)
—
(43)
—
(44)
—
(8)
DEV
(9)
—
(25)
—
—
—
—
—
—
—
Group Apportioned Electric Energy
Interlocked Units Apportioned Electric Energy
PIcontroller Electric Energy 1–4
V
Pulse Input Electric Energy 1–4
Group Apportionment Parameter
Interlocked Units Apportionment Parameter
Room Temp [Water Temp]
V
Error Code Detail
—
Set Temp [Set Water Temp]
Set Temp Cool
Set Temp Heat
V
Set Temp Auto
Set High Limit Setback Temp
Set Low Limit Setback Temp
—
On Off State
Alarm Signal
*2
Filter Sign [Circulating Water Exchange Sign]
M-NET Communication State
V
Night Purge State
Thermo On Off State
System Alarm Signal
External Heat Source State
PIcontroller Alarm Signal
V
On Off Setup
*3
Filter Sign Reset [Circulating Water Exchange Sign Reset]
Prohibition On Off
Prohibition Mode
Prohibition Filter Sign Reset [Prohibition Circulating Water
V
Exchange Sign Reset]
Prohibition Set Temperature
Prohibition Fan Speed
System Forced Off (individual)/(collective)
—
—
—
—
—
—
—
—
—
V
Device object of AE-200/AE-50/EW-50
—
—
12
V: Supported
—: Not supported
Object
*2
*2
*3
*4