9-3-3. Outdoor unit twinning kit
Outdoor unit twinning kit is used to combine multiple outdoor units.
Total capacity of outdoor units
P400 to P650YSNW-A
P700 to P1100YSNW-A
EP400 to EP650YSNW-A
EP700 to EP1100YSNW-A

9-4. Pipe connection example

9-4-1. Example of pipe connection between outdoor units
・PURY-P200YNW-A through PURY-P500YNW-A, and PURY-EP200YNW-A through PURY-EP500YNW-A can be
used in a Hybrid City Multi system. Contact your dealer when connecting the larger capacity units in a
Hybrid City Multi system.
WT08432X01
Kit model
CMY-R100VBK4
CMY-R200VBK4
CMY-R100VBK4
CMY-R200VBK4
GB-23
On-site piping
Twinning Kit
The pipe section before the twinning pipe must
have at least 500 mm (19-11/16 in) of straight
section.