Inspection And Maintenance Types - Toshiba HV6FS-MLD Instruction Manual

Vacuum circuit breakers - drawout type 4.8 & 7.2kv voltage classes fast closing w/uv release
Table of Contents

Advertisement

Page 26
RECOMMENDED INSPECTION AND
MAINTENANCE TYPES
NOTE:
Refer to the SAFETY section of this
manual for important information.
A. Acceptance Inspection
This inspection confirms that the circuit
breaker unit is complete, correct as specified,
and
undamaged
procedure for this inspection is outlined in the
RECEIVING, INSPECTION AND HANDLING
section of this manual.
B. Patrol Inspection
Inspection is made of the condition of the
circuit breaker while it is energized. Check
that no unusual sounds or smells exist
externally.
Inspection Frequency: Once every 6 months
C. Periodic Inspection
Inspection is performed with the circuit breaker
de-energized. The lubrication of sliding and
rotating parts is checked and the mechanism
is lubricated if needed.
Inspection Frequency: Once every 1-3 years
or every 3000 operations (normal).
every 6 years (detailed).
Refer to Table 2 for the schedule of Periodic
Inspections.
D. Unscheduled Inspection
Inspections are implemented as required.
Inspection Frequency: As needed
NOTE:
The inspection frequency and points
to be inspected may vary from the
above recommendations depending
on the status of use, frequency of
switching,
interrupted and other factors.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
from
shipment.
The
Once
amount
of
current
MAINTENANCE
Table 1 Tightening Torques
Screw
Nominal
Tightening Torque
Dia.
M4
15-20 kgf-cm
13-17 in-lb
M5
30-40 kgf-cm
26-34 in-lb
M6
50-65 kgf-cm
43-56 in-lb
M8
120-150 kgf-cm
9-11 ft-lb
M10
250-315 kgf-cm
18-23 ft-lb
M12
450-565 kgf-cm
32-41 ft-lb