NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
• Activate the output reactor during commissioning via parameter p0230 = 1.
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m).
Assignment of output reactor and Power Module
Table 2- 1
Assignment of output reactor and Power Module
Power Module
6SL3310-1PE33-0AA0
6SL3310-1PE33-7AA0
6SL3310-1PE34-6AA0
6SL3310-1PE35-8AA0
6SL3310-1PE36-6AA0
6SL3310-1PE37-4AA0
6SL3310-1PE38-4AA0
6SL3310-1PE38-8AA0
6SL3310-1PE41-0AA0
6SL3310-1PG33-7AA0
6SL3310-1PG34-0AA0
6SL3310-1PG34-5AA0
6SL3310-1PG35-2AA0
6SL3310-1PG35-8AA0
6SL3310-1PG36-5AA0
6SL3310-1PG37-2AA0
10
Rated power of the Power Module
Line voltage 380 – 480 V 3 AC
160 kW
200 kW
250 kW
315 kW
355 kW
400 kW
450 kW
500 kW
560 kW
Line voltage 500 – 690 V 3 AC
315 kW
355 kW
400 kW
450 kW
500 kW
560 kW
630 kW
suitable output reactor
6SL3000-2BE33-2AA0
6SL3000-2BE33-8AA0
6SL3000-2BE35-0AA0
6SL3000-2AE36-1AA0
6SL3000-2AE38-4AA0
6SL3000-2AE38-4AA0
6SL3000-2AE41-0AA0
6SL3000-2AE41-0AA0
6SL3000-2AE41-4AA0
6SL3000-2AH34-7AA0
6SL3000-2AH34-7AA0
6SL3000-2AH35-8AA0
6SL3000-2AH38-1AA0
6SL3000-2AH38-1AA0
6SL3000-2AH38-1AA0
6SL3000-2AH38-1AA0
Operating Instructions, 05/2017, A5E32846921B AE