Analog in 15 bit voltage/current 8ch

Advertisement

ANALOG IN 15 BIT VOLTAGE/CURRENT 8CH IC220ALG221
Technical Data
General Data
Housing dimensions (width x height x depth)
Weight
Operating mode
Type of sensor connection
Permissible temperature (operation)
Permissible temperature (storage/transport)
Permissible humidity (operation)
Between -25°C and +55°C (-13°F to +131°F) appropriate measures against increased
humidity (> 85%) must be taken.
Permissible humidity (storage/transport)
For a short period, slight condensation may appear on the outside of the housing if, for
example, the terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation)
Permissible air pressure (storage/transport)
Degree of protection
Class of protection
Interface
Bus interface
Power Consumption
Communications power U
Current consumption from U
I/O supply voltage U
Current consumption to U
Total power consumption
Supply of the Electronics Module and I/Os Through Bus Terminal/Power Terminal
Connection method
42
L
L
ANA
ANA
48.8 mm x 120 mm x 71.5 mm
(1.921 in. x 4.724 in. x 2.815 in.)
125 g (without connectors)
Process data operation with 2 words
2-wire technology
-25°C to +55°C (-13°F to 131°F)
-25°C to +85°C (-13°F to 185°F)
75% on average, 85% occasionally
75% on average, 85% occasionally
80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level)
IP 20 according to IEC 60529
Class 3 according to VDE 0106 and IEC 60536
Data routing
7.5 V
48 mA, typical/55 mA, maximum
24 V DC
30 mA, typical/35 mA, maximum
1500 mW, typical
Potential routing
6226B_GE