(2) For each control level, set the total time in which
the Peak Cut control is performed during every 30
minutes.
Each Peak Cut control is performed for three
minutes. If [6] minutes is selected, three-minute
Peak Cut control will be performed twice during
every 30 minutes.
If any time other than [30] minutes is selected, the
indoor units will operate in rotation so that they will
not perform the Peak Cut control at the same time.
(3) To copy the settings of a block to the settings for other blocks, display the block whose settings are to be
copied and click [Copy], then display the block to which the copied settings are to be pasted and click [Paste].
The rectangular icons next to the selected buttons will appear in yellow-green.
WT07138X02
When [6] minutes is selected
0
3 5
Group 1
Group 2
Group 3
42
Control time
8 10
13
15 18 20 23 25
28
30
min