Cabinet air conditioning

5.1

General

The minimum dimensions listed below for ventilation clearances must be observed. No other
components or cables must be located in these areas.
NOTICE
Device failure caused by overloading of devices and components
If the guidelines for installing SINAMICS G130 equipment are not observed, this can
significantly reduce the service life of the components and result in premature device and
component failure.
• Observe the guidelines for installing the devices and components.
You must take into account the following specifications when using SINAMICS G130:
● Ventilation clearance
● Wiring and cabling
● Air guidance
Table 5- 1
Ventilation clearances for the components
Component
Power Module
Power Module
Power Module
The clearances refer to the area around the ventilation slots on the front cover.
1)
Note
Notes on the dimensions
The dimensions refer to the outer edges of the devices.
A dimension drawing is available in the Operating Instructions.
Cabinet design and EMC
Operating Instructions, 07/2016, A5E00427629A
Frame size
Clearance (front)
FX
GX
HX, JX
Clearance (above)
[mm]
[mm]
40
1)
50
1)
40
1)
Clearance (below)
[mm]
250
150
250
150
250
150
5