Toshiba DeviceNet DEV003Z-1 Function Manual page 29

For tosvert vf-mb1/s15 converter
Table of Contents

Advertisement

3.4.6.2.
fa23 (Communication command 2)
bit
Function
0
(Reserved)
Electric power quantity
1
reset
2
(Reserved)
3
(Reserved)
4
(Reserved)
5
(Reserved)
6
(Reserved)
Maximum deceleration
7
forced stop
Acceleration/decele-
8
ration selection 1
Acceleration/decele-
9
ration selection 2
10
(Reserved)
11
(Reserved)
12
OC stall level switch
13
(Reserved)
14
(Reserved)
15
(Reserved)
Note: Set 0 to reserved bit.
3.4.6.3.
fa07 (frequency reference from internal option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
3.4.6.4.
fa50 (Terminal output data from communication)
By setting up the data of the bit 0 - 1 of terminal output data (fa50) from communication, setting data (OFF or
ON) can be outputted to the output terminal.
Please select the functional number 92 - 95 as the selection (f130 - f138) of the output terminal function
before using it.
bit
Specified data output
0
(Output terminal No.: 92, 93)
Specified data
1
(Output terminal No.: 94, 95)
2-15
(Reserved)
Note: Set 0 to reserved bit
3.4.6.5.
fa51 (Analog output (FM) data from communication)
Use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication data output).
This makes it possible to send out the data specified as FM analog output data (fa51) though the FM analog
output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the VF-MB1/S15 instruction manual for details.
0
-
OFF
-
-
-
-
-
Normal
00: Acceleration/deceleration 1
01: Acceleration/deceleration 2
10: Acceleration/deceleration 3
-
-
OC stall 1
-
-
-
Output TB function name
1
output 2
- 28 -
1
-
Electric power quantity (fe76,
Reset
fe77) reset
-
-
-
-
-
Enabled
Select
1-4 by combination of two bits..
AD1: acc, dec
AD2: f500, f501
AD3: f510, f511
-
-
OC stall 1: f601
OC stall 2
OC stall 2: f185
-
-
-
0
OFF
OFF
-
E6581737
Note
-
-
-
-
-
-
-
acceleration/deceleration
-
-
-
-
-
1
ON
ON
-

Advertisement

Table of Contents
loading

Table of Contents