Symbols; Derating; Temperature Derating; Altitude Derating - ABB ACS800 Series Hardware Manual

+c236 wind turbine convert for asynchronous slip ring generators
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

104

Symbols

Nominal ratings
I
cont.max
I
max
Typical ratings for no overload use
P
cont.max
Typical ratings for light overload use (10% overloadability)
I
2N
P
N
Typical ratings for heavy duty use (50% overloadability)
I
2hd
P
hd

Derating

The load capacity (current and power) decreases if the installation site altitude exceeds 2000 metres
(6600 ft), or if the ambient temperature exceeds 45°C (113°F).

Temperature derating

In the temperature range +45°C (+113°F) to +50°C (+122°F), the rated output current is decreased by
2% for every additional 1°C (1.8°F). The output current is calculated by multiplying the current given in
the rating table by the derating factor.
Example If the ambient temperature is 50°C (+122°F), the derating factor is 100% - 1
90% or 0.90. The output current is then 0.90 × I
Note: I

Altitude derating

At altitudes from 2000 to 4000 m (6600 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
2000 m (6600 ft) above sea level, please contact your local ABB representative or office for further
information.

Dimensions, noise, cooling characteristics of the modules

Unit
Grid-side converter
Rotor-side converter
LCL filter
LCL filter
See also delivery specific dimensional drawings.
Technical data
Continuous rms output current. No overloadability at 40°C.
Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by converter temperature.
Typical converter output power.
Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
Typical converter output power.
Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Typical converter output power.
rating is not allowed above 45°C (113°F).
cont.max
Frame size
Height
mm
R8i
1397
2×R8i
2×1397
BLCL-15-7
1355
ALCL-15-7
1397
or 0.90 × I
2N
2hd
Width
Depth
mm
mm
240
590.5
2×240
590.5
240
504.9
240
199
%
°C
.
Weight
Noise level
kg
dBA
118
72
300
74
217.5
-
180
-
· 10°C =
Air flow
3
m
/h
1280
2560
400