Mitsubishi Electric PAC-IF032B-E Installation And Operation Manual page 29

Flow temp. controller 2b (cased)
Table of Contents

Advertisement

. Remote controller operation
Should settings be changed from default please enter new setting in 'Field Setting' column. This will ease resetting in the future should the system use change or the circuit
board need to be replaced.
Commissioning/Field settings record sheet
Remote controller screen
Main
DHW max. temp.
Heating mode
Cooling mode
Holiday mode
Menu Water temp. setting
DHW
Heating
Cooling
Holiday
Compensation curve Low outdoor ambient
temp. point
Hi outdoor ambient
temp. point
Initial settings
Language
°C/°F
Temp. display
Time display
Service
Restriction
Temp. offset setting
Temp./Analog signal
20 - 60°C
20 - 60°C
5 - 25°C
Active/Non active/Set time
20 - 60°C
20 - 60°C
5 - 25°C
20 - 45°C
Outdoor ambient temp. −15 - 34°C
Target flow temp.
20 - 60°C
Outdoor ambient temp. −14 - 35°C
Target flow temp.
20 - 60°C
ENG/GER/SP/IT/FR/SW/JP
1°C/1°F
ON/OFF
hh:mm/hh:mm AMPM/AMPM hh:mm
Operation lock
none/Mode&Temp/All
Mode skip
DHW
Heating
Heating Eco Used/Not used (Skipped) Used
Cooling
Holiday
Temp. range
DHW
20 - 60°C
Heating 20 - 60°C
Cooling 5 - 25°C
DHW/Heating
−15 - 15°C
Cooling
−15 - 15°C
DHW/Heating
Target temp. of low signal point
−20 - 90°C
Target temp. of hi signal point
−20 - 90°C
Cooling
Target temp. of low signal point
−20 - 90°C
Target temp. of hi signal point
−20 - 90°C
Default
Parameters
setting
50℃
45℃
15℃
-
50℃
45℃
15℃
35℃
−15℃
50℃
35℃
25℃
ENG
1°C
OFF
hh:mm
none
Used/Not used (Skipped) Used
Used/Not used (Skipped) Used
Used/Not used (Skipped) Used
Used/Not used (Skipped) Used
20 - 60°C
20 - 60°C
5 - 25°C
0℃
0℃
20℃
60℃
5℃
25℃
Field setting
Notes
29