S11 Monitoring

Demand

CURRENT
DEMAND
kW DEMAND
kvar DEMAND
kVA DEMAND
GE Multilin
PATH: SETPOINTS
S11 MONITORING
[ ]
CURRENT DEMAND
PERIOD: 15 min.
CURRENT DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
CURRENT DEMAND
MESSAGE
LIMIT: 100 A
CURRENT DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
kW DEMAND
PERIOD: 15 min.
kW DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
kW DEMAND
MESSAGE
LIMIT: 100 kW
kW DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
kvar DEMAND
PERIOD: 15 min.
kvar DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
kvar DEMAND
MESSAGE
LIMIT: 100 kvar
kvar DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
kVA DEMAND
PERIOD: 15 min.
kVA DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
kVA DEMAND
MESSAGE
LIMIT: 100 kVA
kVA DEMAND
MESSAGE
ALARM EVENTS: Off
The 469 measures motor demand for several parameters (current, kW, kvar, and
kVA). These values may be of interest for energy management programs where
processes may be altered or scheduled to reduce overall demand on a feeder.
Demand is calculated as follows. Every minute, an average magnitude is calculated
for current, +kW, +kvar, and kVA based on samples taken every 5 seconds. These
http://www.GEindustrial.com/multilin
Motor Management Relay
CURRENT DEMAND
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 10 to 100000 A in steps of 1
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kW in steps of 1
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kvar, step 1
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 50000 kVA, step: 1
Range: On, Off
469
5–75