GE DR60 Technical Manual page 31

Table of Contents

Advertisement

DR60
31
The settings tabs contain all configurable parameters of the equipment divided by
categories. There are seven settings tabs, as shown in the figure below.
DR60 Configurator Settings Tabs
Through the setting tabs it is possible to configure all the equipment parameters, as
detailed on the table below. The possible configurations and the procedure to configure
each parameter will be described in the next sections.
Hover the mouse cursor over the text fields of the configurable parameters to show the
range of values or the possible characters.
The table below describes the menu options:
Tab
General
Physical Device
(LPHD)
Analog
Bay
Arrangements
(MMXU/MMXN)
Generic Sensors
(TGSN)
Binary
Binary Inputs
GOOSE Inputs
Physical
Communication
Dataset
GOOSE Publisher
Sub-tab
Contains the values and parameters of the
Physical Device logical node (LPHD), such
as: Model, Identifier, Location etc.
Configures name tags/descriptions and
associates the analog physical terminals to
the measurements circuits, sets the CT/VT
ratios; nominal frequency. Enables
calculations such as: RMS, power,
frequency, symmetrical components, THD,
average values, PMU and impedance fault
location
Configures name parameters for the
transducer inputs ± 10V and 20 mA dc
Configures the voltage level, debouncing
time and polarity of the binary inputs.
Enables and configures the tags of the
GOOSE inputs
Configures parameters related to the
Ethernet and serial ports, such as: PRP
redundancy, IP Address etc.
Adds and edits the datasets to be sent via
GOOSE of MMS
Associates the datasets to GOOSE Control
Blocks to be published.
Description
DR60-TM-EN-2A